INTERNAL UPS DIAGRAM | ||||||||||
| ||||||||||
PFC |
|
| PWM |
|
|
|
|
|
| |
|
| INVERTER |
|
|
|
|
| |||
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| Isolated 120Vac | ||
|
|
|
|
|
|
|
| Output | ||
|
|
|
| Output |
|
|
|
| ||
|
|
|
|
|
|
|
|
| ||
INPUT |
|
| Internal UPS |
|
|
|
|
| ||
|
| Batteries (240Vdc) |
|
|
|
| ||||
RECTIFIER |
|
|
|
|
|
|
|
|
| New Derived |
|
|
|
|
|
|
|
|
|
| |
|
| + |
|
|
|
|
|
|
| 120Vac Neutral |
Battery |
|
|
|
|
|
|
|
|
|
|
Charger |
|
|
|
|
|
|
|
|
|
|
Terminal #1 |
|
|
|
|
|
|
|
|
| Terminal #10 |
Chassis Ground (Input) | + External Battery (+240Vdc) | - External Battery (- 240Vdc) | Output 2 | Output 2 - 120Vac Neutral (White WIre) | Output 1 - | Output 1 - | Chassis Ground (Output 1 & 2) | Terminal Block as Viewed Through | ||
the Opening in the UPS Rear Panel | ||||||||||
|
3.0. Extended Battery Bank Option Installation (hardwire models only)
Optional Extended Battery banks are available for the SG5 & 6kVA models providing extended battery backup up to many hours. Each extended battery
is a completely
Installation Instructions:
1.VERIFY THE BATTERY DISCONNECT CIRCUIT BREAKER IS IN THE “OFF” POSITION PRIOR TO MAKING ANY WIRING CONNECTIONS.
2.Verify the Extended battery Bank is configured properly. Verify the input (models with internal battery chargers only) and DC output voltage. All SG 5 & 6kVA models require the use of an external battery bank with an output of 240Vdc @ 30A. This information is stated on the nameplate label located on the rear or the side panel of the unit.