Falcon SG6K-2TC, SG5K-1TXC, SG5K-2TXC DRY Contact & Opto Coupler Interface Board Options

Page 24

DRY CONTACT & OPTO COUPLER INTERFACE BOARD OPTIONS

Typical Falcon Dry Contact Relay Board

DB-9

JP1

J1

JP2

J2

JP3

J3

PIN & JUMPER ASSIGNMENT FOR THE FALCON

UA88374 RELAY OPTION BOARD

(no on-bypass signal)

PIN

DESCRIPTION

1Low Battery ( When UPS reaches low battery, contact activates) (J1, 1-2 short = N.O) (J1, 2-3 short = N.C)

2JP2 shorted = Low Battery common & all other shorted JP commons JP2 open = common for low battery only

3Utility Loss N.O. ( At loss of utility voltage, contact activates)

4Utility Loss N.C. ( At loss of utility voltage, contact activates)

5JP1 shorted = Utility Loss common & all other shorted JP commons JP1 open = Utility Loss common only

6Remote Shutdown common

7Remote Shutdown

(J2, 1-2 short = outside power) (J2, 2-3 short = inside power)

1-2 shorted. Applying an external 12V signal across the DB-9, pins six and seven, while the UPS is on battery, will turn the UPS off.

2-3 shorted. Applying a short directly across the DB-9, pins six and seven, while the UPS is on battery, will turn the UPS off.

8Alarm (Upon a UPS fault or failure the contact activates) (J3, 1-2 short = N.O.) (J3, 2-3 short = N.C.)

9JP3 shorted = Alarm common & all other shorted JP commons JP3 open = Alarm common only

 

PIN & JUMPER ASSIGNMENT FOR THE FALCON

 

UA88376 RELAY OPTION BOARD

 

(with on-bypass signal)

 

 

 

DB-9F PIN & JUMPER ASSIGNMENTS

PIN

DESCRIPTION

1Low Battery ( When UPS reaches low battery, contact activates) (J1, 1-2 short = N.O) (J1, 2-3 short = N.C)

2JP2 shorted = Low Battery common & all other shorted JP commons JP2 open = common for low battery only

3Utility Loss N.O. ( At loss of utility voltage, contact activates)

4Utility Loss N.C. ( At loss of utility voltage, contact activates)

5JP1 shorted = Utility Loss common & all other shorted JP commons JP1 open = Utility Loss common only

6Remote Shutdown common

7Remote Shutdown

(J2, 1-2 short = outside power) (J2, 2-3 short = inside power)

1-2 shorted. Applying an external 12V signal across the DB-9, pins six and seven, while the UPS is on battery, will turn the UPS off.

2-3 shorted. Applying a short directly across the DB-9, pins six and seven, while the UPS is on battery, will turn the UPS off.

8On Bypass or Alarm (Upon the UPS going to bypass or a UPS failure the contact activates)

(J3, 1-2 short = N.O.) (J3, 2-3 short = N.C.)

9JP3 shorted = On bypass, Alarm common & all other shorted JP commons

JP3 open = On bypass, Alarm common only

22

Image 24
Contents Owners Operating Manual Table of Contents SG Series ON-LINE UPS System Block Diagram Important Safety Instructions Electric, IncInput Power Factor Correction Extended Battery Bank OptionTrue Regenerative On-Line Design Microprocessor ControlInstallation Instructions General Common for all modelsDisregard On Designation Leveling Feet Adjustment Model View of the Input/Output Hardwire Terminal Block UPS Output RequirementsOutput Requirements Do not USE the Upper Terminal ConnectionsInternal UPS Diagram SG5K-2TC & SG6K-2TCInstallation Instructions SG5K-2TXC & SG6K-2TXCExtended Battery Bank Selection Guide USE Copper Conductors only Model Required ReceptacleUPS Output Details Output Power Distribution Center Typical Power Distribution Center ConfigurationRefer to page 20 for Operating Instructions Extended Battery Bank DC Interconnection All models except hardwireInstallation Procedure Load Level Indicator LEDs Battery Level Indicator LEDsLine / Site Wiring Fault Indicator LED Battery Mode Indicator LEDBypass Indicator LED Inverter Indicator LEDGreen Mode LED Indicator Over Crest Indicator LEDAudible Alarms Category one alarmsCategory two alarms Page Communications Interfaces LocationSupported Protocols DRY Contact & Opto Coupler Interface Board Options PIN Assignment for the Falcon Care & Maintenance Battery Life vs. TemperatureBattery Replacement Storing the UPS and Batteries FCC ConsiderationsTechnical Support Requesting Technical Information or SupportSUPPORT@FALCONUPS.COM 800.842.6940 Falcon Web SupportWarranty General Provisions6kVA Models