Falcon SG5K-2TC, SG6K-2TC, SG5K-1TXC, SG5K-2TXC, SG6K-1TX specifications 6kVA Models

Page 30

SG SeriesTM UPS PLUS®

5-6kVA MODELS

 

 

Model Number

SG5K -1TX & -

SG5K -2TX &

SG5K -2T

SG6K-1TX

SG6K-2TX &

SG6K-2T

-1TXC

-2TXC

& -2TC

 

-2TXC

& -2TC

 

 

Nominal VA

5000

5000

5000

6000

6000

6000

Electrical Input

Nominal AC Voltage

120V

230V

230V

 

120V

 

230V

230V

AC Voltage Range

87-140V

170-275V

170-275V

 

87-140V

 

170-275V

170-275V

Current-Amps

38.7

20.3

19.5

 

46.6

 

24.3

23.4

Frequency

 

 

50/60

Hz ±5%

 

 

 

Efficiency (Typical)

 

> 79%

> 82%

 

 

> 79%

> 82%

Power Factor Correction

 

 

 

>

0.95

 

 

 

Electrical Output

Watts

 

3500

 

 

 

 

4200

 

 

 

120 & 208V or

(1)

 

208V

208V

 

120 & 208V or

(1)

208V

208V

AC Voltage

120 & 220V or

120V

 

220V

220V

 

120 & 220V or

120V

220V

220V

(Switchable except where noted)

120 & 240V

(1)

 

230V

230V

 

120 & 240V

(1)

230V

230V

 

(No Switching)

(1)

 

240V

240V

 

(No Switching)

(1)

240V

240V

Isolation Transformer

No

Yes

 

No

No

 

No

Yes

No

No

Frequency

60Hz

50/60Hz

 

50/60Hz

50/60Hz

 

60Hz

50/60Hz

50/60Hz

50/60Hz

Voltage Regulation

 

±4%

 

 

±3%

 

 

±4%

 

±3%

Frequency Stability

 

 

 

 

± 0.3% (Battery Mode)

 

 

 

Step Load Change

 

 

 

 

±7% for 100% load variation

 

 

 

THD – Linear Loads

 

 

 

 

 

< 3%

 

 

 

THD – Non-Linear Loads

 

< 7%

 

 

<5%

 

 

< 7%

 

<5%

Overload

 

 

 

 

105% for

50 Seconds

 

 

 

Crest Ratio

 

 

 

 

 

3:1

 

 

 

(1)Contact the factory for output settings.

.

Battery

DC Voltage

 

 

240V

Type

 

 

12V, 7AH Sealed Lead Acid Maintenance-Free

Back Up Time

@ Full Load

9 Minutes

 

7 Minutes

 

@ 1/2 Load

28 Minutes

 

18 Minutes

Recharge Time

 

 

10 Hours to 90%

Battery times are approximate.

 

 

 

Electrical Connections Input

-1TX

Hardwire

-1TXC

L5-50P

-2T

 

-2TC

 

-2TX

 

-2TXC

 

Hardwire

L6-30P

Hardwire

L6-30P

Hardwire

Hardwire

L6-30P

Hardwire

L6-30P

Electrical Connections Output

-1TX

Hardwire

 

(2) duplex

-1TXC

5-20R &

 

(1) L6-30R

-2T

 

-2TC

 

-2TX

 

-2TXC

 

 

 

Hardwire

(1) L6-30R

Hardwire

(2)duplex 5-20R &

(1)L6 -30R

Hardwire

Hardwire

(1) L6-30R

Hardwire

(2)duplex 5-20R &

(1)L6-30R

Contact the factory for other input/output options.

Environmental

Operating Temperature

0º C to 35º C (32º F to 95º F)

Humidity

10% to 95% Non – Condensing

Altitude

7,000 Feet

Cooling

Low Velocity Forced Air Fans

Audible Noise @ 1 Meter

< 55dBA

Controls and Indicators

LED

Line, Inverter, Battery Reserve, Load, Bypass, Alarm, Crest, Battery & Load Capacity Level

Audible Alarms

DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temp., Over Load, Fault Alarm

Communications

RS-232 Serial Port (Bundled UPSilon 2000 Software)

Mechanical

Dimensions H x W x D

inches

Hardwired Models

 

32.1 x 10.2 x 21.8

(815.3 x 259.0 x 553.7)

 

(mm)

Receptacle Models

 

32.1 x 10.2 x 27.0

(815.3 x 259.0 x 685.8)

Weight

lb. (kg)

T

 

 

216

(98)

 

 

 

TX

 

 

299

(136)

 

 

 

TC

 

 

239

(108)

 

 

 

TXC

 

 

322

(146)

 

Agency Listing

 

UL1778, CUL,

 

-2T:

UL1778, CUL, FCC Class A, CE

UL1778, CUL,

-2T: UL1778, CUL, FCC Class A, CE

 

FCC Class A

 

All others: UL1778, CUL, FCC Class A

FCC Class A

All other s: UL1778, CUL, FCC Class A

 

 

 

Available Options: Extended Run Time Battery Packs, Make-Before-Break Maintenance Bypass, SNMP/HTTP Network Card,

Frequency & Voltage Conversion.

©2004 Falcon® Electric, Inc. All rights reserved. Falcon ® and the Falcon Electric logo are registered trademarks of Falcon Electric, Inc. All other brand names and trademarks are the property of their respective owners.

The information and specifications stated in this document are subject to change without notice.

28

Image 30
Contents Owners Operating Manual Table of Contents SG Series ON-LINE UPS System Block Diagram Important Safety Instructions Electric, IncTrue Regenerative On-Line Design Input Power Factor CorrectionExtended Battery Bank Option Microprocessor ControlInstallation Instructions General Common for all modelsDisregard On Designation Leveling Feet Adjustment Model Output Requirements View of the Input/Output Hardwire Terminal BlockUPS Output Requirements Do not USE the Upper Terminal ConnectionsInternal UPS Diagram SG5K-2TC & SG6K-2TCInstallation Instructions SG5K-2TXC & SG6K-2TXCExtended Battery Bank Selection Guide USE Copper Conductors only Model Required ReceptacleUPS Output Details Output Power Distribution Center Typical Power Distribution Center ConfigurationRefer to page 20 for Operating Instructions Extended Battery Bank DC Interconnection All models except hardwireInstallation Procedure Line / Site Wiring Fault Indicator LED Load Level Indicator LEDsBattery Level Indicator LEDs Battery Mode Indicator LEDGreen Mode LED Indicator Bypass Indicator LEDInverter Indicator LED Over Crest Indicator LEDAudible Alarms Category one alarmsCategory two alarms Page Communications Interfaces LocationSupported Protocols DRY Contact & Opto Coupler Interface Board Options PIN Assignment for the Falcon Care & Maintenance Battery Life vs. TemperatureBattery Replacement Storing the UPS and Batteries FCC ConsiderationsSUPPORT@FALCONUPS.COM Technical SupportRequesting Technical Information or Support 800.842.6940 Falcon Web SupportWarranty General Provisions6kVA Models