Falcon SG6K-2TC, SG5K-1TXC, SG5K-2TXC, SG5K-2TC, SG6K-1TX specifications Model

Page 9

Installation Instructions For Hardwire Models (see model numbers referenced below)

1.0UPS Input & Output Requirements.

IMPORTANT

Note: All SG Series hardwire UPS models must be installed by a licensed electrician, in accordance with the National Electrical Code (NEC) ANSI/NFPA70 and all local regulations. It is further required that the input of SG Series hardwire UPS be wired to a building service panel incorporating a dedicated “branch rated” circuit breaker of the proper rating.

 

 

 

INPUT REQUIREMENTS

 

 

 

MODEL

 

 

REQUIRED INPUT

 

 

 

 

 

 

CIRCUIT BREAKER

SG5K-1TX:- 120Vac, 50/50Hz, 38.7A, 1 phase, 3 wire

 

50A

SG5K-2T - 208-240Vac, 50/60Hz, 19.5A, 1 phase, 3 wire

 

30A

SG5K-2TX - 208-240Vac, 50/60Hz, 20.3A, 1 phase, 3 wire

30A

SG6K-1TX - 120Vac, 50/60Hz, 46.6A, 1 phase, 3 wire

 

70A

SG6K-2T - 208-240Vac, 50/60Hz, 23.4A, 1 phase, 3 wire

 

30A

SG6K-2TX - 208-240Vac, 50/60Hz, 24.3A, 1 phase, 3 wire

30A

 

 

 

 

 

 

 

 

 

 

 

WIRE GAUGE CHART

 

 

 

 

MODEL

AC INPUT

AC OUTPUT(S)

EXTERNAL

 

 

 

-1 = 120 Vac

120 Vac

208-240 Vac

BATTERY

 

 

 

-2 = 208-240 Vac

 

 

 

240 dc

 

 

 

 

 

 

 

 

 

SG5K-1TX

8 Awg. 600V

10 Awg. 600V

 

12 Awg. 600V

10 Awg. 600V

 

 

 

75°C CU

75°C CU

 

75°C CU

75°C CU

 

 

SG5K-2T

12 Awg. 600V

N/A

 

12 Awg. 600V

10 Awg. 600V

 

 

 

75°C CU

 

75°C CU

75°C CU

 

 

 

 

 

 

 

SG5K-2TX

12 Awg. 600V 75°C

10 Awg. 600V

 

12 Awg. 600V

10 Awg. 600V

 

 

 

CU

75°C CU

 

75°C CU

75°C CU

 

 

SG6K-1TX

6 Awg. 600V

8 Awg. 600V

 

10 Awg. 600V

10 Awg. 600V

 

 

 

75°C CU

75°C CU

 

75°C CU

75°C CU

 

 

SG6K-2T

10 Awg. 600V

N/A

 

10 Awg. 600V

10 Awg. 600V

 

 

 

75°C CU

 

75°C CU

75°C CU

 

 

 

 

 

 

 

SG6K-2TX

10 Awg. 600V 75°C

8 Awg. 600V

 

10 Awg. 600V

10 Awg. 600V

 

 

 

CU

75°C CU

 

75°C CU

75°C CU

 

 

External Battery &

16 Awg, 600V

N/A

 

N/A

10 Awg. 600V

 

 

Charger System

75°C CU

 

75°C CU

 

 

 

 

 

ONLY USE WIRE WITH SOLID COPPER CONDUCTORS FOR ALL INPUT/OUTPUT/BATTERY WIRING

SCREW TORQUE SPECIFICATIONS FOR

INPUT/OUTPUT WIRING BLOCK

UPS & BATTERY BANK

 

 

Wire Gauge

Torque

 

 

 

(inch pounds)

 

 

18 - 10 Awg.

20

 

 

8-6 Awg

25 - 30

CAUTION

To reduce the risk of fire, connect only to a circuit providing over-current protection incorporating the specified "branch rated" over-current protection device in accordance with the National Electrical Code, ANSI/NFPA 70.

7

Image 9
Contents Owners Operating Manual Table of Contents SG Series ON-LINE UPS System Block Diagram Electric, Inc Important Safety InstructionsExtended Battery Bank Option Input Power Factor CorrectionTrue Regenerative On-Line Design Microprocessor ControlGeneral Common for all models Installation InstructionsDisregard On Designation Leveling Feet Adjustment Model UPS Output Requirements View of the Input/Output Hardwire Terminal BlockOutput Requirements Do not USE the Upper Terminal ConnectionsSG5K-2TC & SG6K-2TC Internal UPS DiagramSG5K-2TXC & SG6K-2TXC Installation InstructionsExtended Battery Bank Selection Guide USE Copper Conductors only Model Required ReceptacleUPS Output Details Typical Power Distribution Center Configuration Output Power Distribution CenterRefer to page 20 for Operating Instructions Extended Battery Bank DC Interconnection All models except hardwireInstallation Procedure Battery Level Indicator LEDs Load Level Indicator LEDsLine / Site Wiring Fault Indicator LED Battery Mode Indicator LEDInverter Indicator LED Bypass Indicator LEDGreen Mode LED Indicator Over Crest Indicator LEDAudible Alarms Category one alarmsCategory two alarms Page Communications Interfaces LocationSupported Protocols DRY Contact & Opto Coupler Interface Board Options PIN Assignment for the Falcon Care & Maintenance Battery Life vs. TemperatureBattery Replacement FCC Considerations Storing the UPS and BatteriesRequesting Technical Information or Support Technical SupportSUPPORT@FALCONUPS.COM 800.842.6940 Falcon Web SupportGeneral Provisions Warranty6kVA Models