Falcon SG6K-2TC, SG5K-1TXC, SG5K-2TXC, SG5K-2TC, SG6K-1TX Extended Battery Bank Selection Guide

Page 13

3.Select a suitable location for the the extended battery bank, preferably close to the UPS to minimize the risk of DC voltage drop due to excessive long wiring runs. Use 10 Awg, 600V insulated wire for all hardwired DC connections between the UPS and battery bank(s). See Wire Guage Chart of page 7.

VERIFY THE FLOOR OR SURFACE SUPPORTING THE UPS WILL SUPPORT THE WEIGHT OF THE UPS AND ANY OPTIONAL EXTENDED BATTERY BANKS.

FLOOR STANDING EXTENDED BATTERY BANKS = 363 lbs. (165 kg) MAX. (EACH BANK)

4.Remove the lower wiring access cover plate located on the rear panel of the battery bank.

5.Remove the knock-outs from the conduit connector plate located above the previous plate removed. Next, using conduit connectors, install the conduit between the UPS, utility power source (models with battery chargers only) and any other extended battery banks to be installed.

6.Install all of the required wiring. Reference the tables on page 7 for wire Gauge and terminal block torque specifications.

7.Verify all wiring connection to the battery bank(s), UPS and utility sources prior to ` turning on any circuit beakers or equipment power switches.

8.ALWAYS TURN ON THE BATTERY BANK DC DISCONNECT(S) AND THE UPS BATTERY CIRCUIT BREAKER PRIOR TO SWITCHING ON THE UPS AC INPUT CIRCUIT BREAKER.

EXTENDED BATTERY BANK SELECTION GUIDE

(Please specify a hardwire configuration at the time of order)

 

BATTERY OPTION

 

 

 

 

 

 

MODELS

SGB2S7-6K6

SGB2S7-6K6

SGB2S7-6K6

SGB2S7-6K6

SGB2S7-6K6

 

W/O Charger

 

 

 

 

 

 

BATTERIES

40 Pieces 12V,

80 Pieces 12V, 7AH

60 Pieces 12V,

80 Pieces 12V, 7AH

160 Pieces 12V,

 

7AH

 

7AH

 

7AH

 

 

 

 

 

 

BATTERIES IN UPS

 

 

20 each of 12V, 7AH

 

 

 

# of CASES

1 Floor Standing

2 Floor Standing

3 Floor Standing

4 Floor Standing

8 Floor Standing

 

Inches

32.1 x 10.2 x 21.8

32.1 x 10.2 x 21.8

32.1 x 10.2 x 21.8

32.1 x 10.2 x 21.8

32.1 x 10.2 x 21.8

 

(mm)

(814 x 259 x 554)

(814 x 259 x 554)

(814 x 259 x 554))

(814 x 259 x 554)

(814 x 259 x 554)

 

RUN TIME @ 1000W

190 Min.

340 Min.

500 Min.

820 Min.

1400 Min.

 

RUN TIME @ 1750W

92 Min.

180 Min.

265 Min.

450 Min.

740 Min.

 

RUN TIME @ 2500W

60Min.

112 Min.

180 Min.

305 Min.

505 Min.

 

RUN TIME @ 3500W

37.5 Min.

78 Min.

120 Min.

210 Min.

340 Min.

 

5kVA Full Load

 

 

 

 

 

 

 

RUN TIME @ 4200W

29 Min.

60 Min.

92 Min.

165 Min.

270 Min.

 

6kVA Full Load

 

 

 

 

 

 

 

 

 

 

CHARGER OPTION INFORMATION

 

 

 

BATTERY OPTION

 

 

 

 

 

 

 

MODELS

 

SGB2S7 -6K6-1

SGB2S7-6K6-1

SGB2S7-6K6-1

SGB2S7-6K6-1

SGB2S7-6K6-1

 

With 120Vac Charger

 

 

 

 

 

 

 

BATTERY OPTION

 

 

 

 

 

 

 

MODELS

 

SGB2S7 -6K6-2

SGB2S7-6K6-2

SGB2S7-6K6-2

SGB2S7-6K6-2

SGB2S7-6K6-2

 

With 200-240Vac

 

 

 

 

 

 

 

 

 

Charger

 

 

 

 

 

 

 

CHARGER OUTPUT

275Vdc @ 1.3A

275Vdc @ 1.3A

275Vdc @ 1.3A

275Vdc @ 1.3A

275Vdc @ 1.3A

 

# OF CHARGERS

1

2

3

4

8

 

 

 

 

 

 

 

 

 

 

 

Battery run times are for reference only and may vary due to application, environment and the condition of the batteries.

11

Image 13
Contents Owners Operating Manual Table of Contents SG Series ON-LINE UPS System Block Diagram Electric, Inc Important Safety InstructionsExtended Battery Bank Option Input Power Factor CorrectionTrue Regenerative On-Line Design Microprocessor ControlGeneral Common for all models Installation InstructionsDisregard On Designation Leveling Feet Adjustment Model UPS Output Requirements View of the Input/Output Hardwire Terminal BlockOutput Requirements Do not USE the Upper Terminal ConnectionsSG5K-2TC & SG6K-2TC Internal UPS DiagramSG5K-2TXC & SG6K-2TXC Installation InstructionsExtended Battery Bank Selection Guide USE Copper Conductors only Receptacle Model RequiredUPS Output Details Typical Power Distribution Center Configuration Output Power Distribution CenterRefer to page 20 for Operating Instructions All models except hardwire Extended Battery Bank DC InterconnectionInstallation Procedure Battery Level Indicator LEDs Load Level Indicator LEDsLine / Site Wiring Fault Indicator LED Battery Mode Indicator LEDInverter Indicator LED Bypass Indicator LEDGreen Mode LED Indicator Over Crest Indicator LEDCategory one alarms Audible AlarmsCategory two alarms Page Location Communications InterfacesSupported Protocols DRY Contact & Opto Coupler Interface Board Options PIN Assignment for the Falcon Battery Life vs. Temperature Care & MaintenanceBattery Replacement FCC Considerations Storing the UPS and BatteriesRequesting Technical Information or Support Technical SupportSUPPORT@FALCONUPS.COM 800.842.6940 Falcon Web SupportGeneral Provisions Warranty6kVA Models