Falcon SG6K-1TX, SG6K-2TC, SG5K-1TXC, SG5K-2TXC, SG5K-2TC specifications PIN Assignment for the Falcon

Page 25

Typical Falcon Opto-coupler Interface Card

 

PIN ASSIGNMENT FOR THE FALCON

 

UA88373 OPTO-COUPLER OPTION BOARD

 

(no-bypass signal)

 

 

PIN

DESCRIPTION

1

Not Used

2

Utility Loss (N.O.) (Closes upon utility loss)

3

Utility Loss (N.C.) (Opens upon utility loss)

4

Common for pins 2, 3 & 5

5

Low Battery (N.O.) (Closes at low battery)

6

Remote Shutdown

 

Applying a +5-+12Vdc voltage level for >500ms,

 

while the UPS is on battery will shutdown the

 

UPS

7

Not Used

8

Not Used

9

Not Used

OPTO Board Internal Circuitry

 

(B)

(K)

Utility Loss

 

(E)

 

 

 

 

 

 

(C)

 

(A)

 

DB-9

 

 

 

 

 

 

 

6

 

 

 

 

7

2

 

 

 

 

To CPU

 

 

8

3

 

 

 

4

 

 

 

 

 

 

 

 

5

Alarm Signal

Low Battery Signal

23

Image 25
Contents Owners Operating Manual Table of Contents SG Series ON-LINE UPS System Block Diagram Electric, Inc Important Safety InstructionsExtended Battery Bank Option Input Power Factor CorrectionTrue Regenerative On-Line Design Microprocessor ControlGeneral Common for all models Installation InstructionsDisregard On Designation Leveling Feet Adjustment Model UPS Output Requirements View of the Input/Output Hardwire Terminal BlockOutput Requirements Do not USE the Upper Terminal ConnectionsSG5K-2TC & SG6K-2TC Internal UPS DiagramSG5K-2TXC & SG6K-2TXC Installation InstructionsExtended Battery Bank Selection Guide USE Copper Conductors only Receptacle Model RequiredUPS Output Details Typical Power Distribution Center Configuration Output Power Distribution CenterRefer to page 20 for Operating Instructions All models except hardwire Extended Battery Bank DC InterconnectionInstallation Procedure Battery Level Indicator LEDs Load Level Indicator LEDsLine / Site Wiring Fault Indicator LED Battery Mode Indicator LEDInverter Indicator LED Bypass Indicator LEDGreen Mode LED Indicator Over Crest Indicator LEDCategory one alarms Audible AlarmsCategory two alarms Page Location Communications InterfacesSupported Protocols DRY Contact & Opto Coupler Interface Board Options PIN Assignment for the Falcon Battery Life vs. Temperature Care & MaintenanceBattery Replacement FCC Considerations Storing the UPS and BatteriesRequesting Technical Information or Support Technical SupportSUPPORT@FALCONUPS.COM 800.842.6940 Falcon Web SupportGeneral Provisions Warranty6kVA Models