Falcon SG5K-1TXC UPS Output Requirements, View of the Input/Output Hardwire Terminal Block

Page 10

2.0.UPS Output Requirements

IMPORTANT

Note: The outputs of SG 5 & 6kVA models are not configured for 208 or 240Vac split-phase operation. Please reference the output configuration diagrams on pages 9-10 prior to making any wiring connections to the UPS. Should a 208 or 240Vac split-phase output configuration be required, please contact the factory.

MODEL

OUTPUT REQUIREMENTS

RECOMMENDED OUTPUT

 

 

 

CIRCUIT BREAKER

SG5K-1TX:

 

 

Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire

30A

Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1)

50A

SG5K-2T

 

 

Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire

30A

Output 2: None

 

 

SG5K-2TX

 

 

Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire

30A

Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1)

50A

SG6K-1TX

 

 

Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire

30A

Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1)

50A

SG6K-2T

 

 

Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire

30A

Output 2: None

 

 

SG6K-2TX

 

 

Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire

30A

Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1)

50A

Terminal Designation Numbers 1 2 3 4 5 6 7 8 9 10

View of the Input/Output Hardwire Terminal Block

This terminal block is located on the UPS rear panel and shown with the conduit mounting and

access cover plates removed.

Use only the lower terminals and wire securing screws when making wiring connections to

the UPS.

DO NOT USE THE UPPER TERMINAL CONNECTIONS

Refer to the Wire Gauge Table on Page 7 for recommended wire sizes.

Refer to the Torque Specification Table on Page 7 and tighten all 20 screws as specified. Refer to Pages 9-10 for the terminal wiring designations for your specific SG UPS model.

8

Image 10
Contents Owners Operating Manual Table of Contents SG Series ON-LINE UPS System Block Diagram Important Safety Instructions Electric, IncTrue Regenerative On-Line Design Input Power Factor CorrectionExtended Battery Bank Option Microprocessor ControlInstallation Instructions General Common for all modelsDisregard On Designation Leveling Feet Adjustment Model Output Requirements View of the Input/Output Hardwire Terminal BlockUPS Output Requirements Do not USE the Upper Terminal ConnectionsInternal UPS Diagram SG5K-2TC & SG6K-2TCInstallation Instructions SG5K-2TXC & SG6K-2TXCExtended Battery Bank Selection Guide USE Copper Conductors only Receptacle Model RequiredUPS Output Details Output Power Distribution Center Typical Power Distribution Center ConfigurationRefer to page 20 for Operating Instructions All models except hardwire Extended Battery Bank DC InterconnectionInstallation Procedure Line / Site Wiring Fault Indicator LED Load Level Indicator LEDsBattery Level Indicator LEDs Battery Mode Indicator LEDGreen Mode LED Indicator Bypass Indicator LEDInverter Indicator LED Over Crest Indicator LEDCategory one alarms Audible AlarmsCategory two alarms Page Location Communications InterfacesSupported Protocols DRY Contact & Opto Coupler Interface Board Options PIN Assignment for the Falcon Battery Life vs. Temperature Care & MaintenanceBattery Replacement Storing the UPS and Batteries FCC ConsiderationsSUPPORT@FALCONUPS.COM Technical SupportRequesting Technical Information or Support 800.842.6940 Falcon Web SupportWarranty General Provisions6kVA Models