Falcon SG6K-2TC, SG5K-1TXC, SG5K-2TXC Communications Interfaces, Location, Supported Protocols

Page 23

CHAPTER 4

COMMUNICATIONS INTERFACES

RS-232 INTERFACE

Location:

The RS-232 interface is standard on all SG series UPS models. The port is located on the UPS rear panel, via a DB-9 female connector.

Supported Protocols

UPSILON 2000 & SEC SmartMon

BAUD RATE -------

2400bps

DATA LENGTH----

8 bits

STOP BIT-----------

1 bit

PARITY--------------

None

1

2

3

4

5

6

7TX

8

 

GND

 

GEN

9

 

RX

 

 

DB-9 Connector Pin Assignment

Pin #

Function explanation

I/O

9

RS 232 Rx

INPUT

6

RS 232 Tx

OUTPUT

7

Ground

 

CAUTION

When making a connection between a computer and the UPS RS-232 port, always use the green cable supplied with the UPS.

CAUTION

There are communications options that WILL DISABLE the RS-232 port and render it inoperable. The options are as follows:

a.Internal SNMP/HTTP agent option installed into the UPS communications option slot.

The following options WILL NOT affect the operation of the RS-232 port:

a.Falcon Opto Coupler based signal interface board installed in the communications option slot.

b.Any Falcon relay-based, dry contact signal interface board installed in the communications option slot.

CAUTION

DB-9 Signals are not isolated and intended for connection to like RS-232 interfaces. DO NOT APPLY ANY OTHER VOLTAGES TO THESE PINS!

21

Image 23
Contents Owners Operating Manual Table of Contents SG Series ON-LINE UPS System Block Diagram Electric, Inc Important Safety InstructionsMicroprocessor Control Input Power Factor CorrectionExtended Battery Bank Option True Regenerative On-Line DesignGeneral Common for all models Installation InstructionsDisregard On Designation Leveling Feet Adjustment Model Do not USE the Upper Terminal Connections View of the Input/Output Hardwire Terminal BlockUPS Output Requirements Output RequirementsSG5K-2TC & SG6K-2TC Internal UPS DiagramSG5K-2TXC & SG6K-2TXC Installation InstructionsExtended Battery Bank Selection Guide USE Copper Conductors only UPS Output Details Model RequiredReceptacle Typical Power Distribution Center Configuration Output Power Distribution CenterRefer to page 20 for Operating Instructions Installation Procedure Extended Battery Bank DC InterconnectionAll models except hardwire Battery Mode Indicator LED Load Level Indicator LEDsBattery Level Indicator LEDs Line / Site Wiring Fault Indicator LEDOver Crest Indicator LED Bypass Indicator LEDInverter Indicator LED Green Mode LED IndicatorCategory two alarms Audible AlarmsCategory one alarms Page Supported Protocols Communications InterfacesLocation DRY Contact & Opto Coupler Interface Board Options PIN Assignment for the Falcon Battery Replacement Care & MaintenanceBattery Life vs. Temperature FCC Considerations Storing the UPS and Batteries800.842.6940 Falcon Web Support Technical SupportRequesting Technical Information or Support SUPPORT@FALCONUPS.COMGeneral Provisions Warranty6kVA Models