6.Select a suitable location for the UPS.

VERIFY THE FLOOR OR SURFACE SUPPORTING THE UPS WILL SUPPORT THE

WEIGHT OF THE UPS AND ANY OPTIONAL EXTENDED BATTERY BANKS.

SG5K-2T & SG6K-2T UPS MODELS = 216 lbs. (98 kg) SG5K-2TC & SG6K-2TC UPS MODELS = 239 lbs. (108 kg)

SG5K-1TX, SG5K-2TX, SG6K-1TX, SG6K-2TX UPS MODELS = 299 lbs. (136 kg) SG5K-1TXC, SG5K-2TXC, SG6K-2TXC UPS MODELS = 322 lbs. (146 kg)

FLOOR STANDING EXTENDED BATTERY BANKS = 363 lbs. (165 kg) MAX. (EACH BANK)

7.If extended battery banks are to be connected to the UPS, please refer to page 7 for hardwire models and page 16 for all other models.

8.If unattended computer shutdown and monitoring are desired, connect the green UPS/Computer cable to the DB-9 connector located on the UPS rear panel. Then install the shutdown and monitoring software provided with the UPS. For your reference, UNIX shutdown and monitoring software is available from Falcon Electric at an additional cost.

9.Verify the location selected has adequate ventilation to allow for the proper cooling of the UPS.

DO NOT BLOCK UPS FANS OR AIR VENTS. THE UPS MUST NOT BE INSTALLED IN AN ENCLOSED AREA.

10.For further installation instructions covering hardwire models SG5K-1TX, SG5K-2T, SG6K-1TX, SG6K-2T and SG6K-2TX, please refer to page 7.

11.Lower the leveling feet.

a.Verify the flooring at the UPS or battery bank installation location is rated for the weight of the equipment.

b.Roll the UPS or extended battery bank to the final installation location.

c.Locate the position of the (4) levelling feet underneath the UPS near its four corners. (see picture below).

d.Using your fingers and a 12mm open end wrench, screw the levelling feet in a clockwise direction, lowering the feet until all four feet are securely against the floor.

12.For further installation details covering the following models having a line cord and PDU, please refer to page 13. Models SG5K-1TXC, SG5K-2TC, SG5K-2TXC,

SG6K-2TC and SG6K-2TXC.

Leveling Feet Adjustment

6

Image 8
Contents Owners Operating Manual Table of Contents SG Series ON-LINE UPS System Block Diagram Important Safety Instructions Electric, IncInput Power Factor Correction Extended Battery Bank OptionTrue Regenerative On-Line Design Microprocessor ControlInstallation Instructions General Common for all modelsDisregard On Designation Leveling Feet Adjustment Model View of the Input/Output Hardwire Terminal Block UPS Output RequirementsOutput Requirements Do not USE the Upper Terminal ConnectionsInternal UPS Diagram SG5K-2TC & SG6K-2TCInstallation Instructions SG5K-2TXC & SG6K-2TXCExtended Battery Bank Selection Guide USE Copper Conductors only UPS Output Details Model RequiredReceptacle Output Power Distribution Center Typical Power Distribution Center ConfigurationRefer to page 20 for Operating Instructions Installation Procedure Extended Battery Bank DC InterconnectionAll models except hardwire Load Level Indicator LEDs Battery Level Indicator LEDsLine / Site Wiring Fault Indicator LED Battery Mode Indicator LEDBypass Indicator LED Inverter Indicator LEDGreen Mode LED Indicator Over Crest Indicator LEDCategory two alarms Audible AlarmsCategory one alarms Page Supported Protocols Communications InterfacesLocation DRY Contact & Opto Coupler Interface Board Options PIN Assignment for the Falcon Battery Replacement Care & MaintenanceBattery Life vs. Temperature Storing the UPS and Batteries FCC ConsiderationsTechnical Support Requesting Technical Information or SupportSUPPORT@FALCONUPS.COM 800.842.6940 Falcon Web SupportWarranty General Provisions6kVA Models