6.Select a suitable location for the UPS.
VERIFY THE FLOOR OR SURFACE SUPPORTING THE UPS WILL SUPPORT THE
WEIGHT OF THE UPS AND ANY OPTIONAL EXTENDED BATTERY BANKS.
FLOOR STANDING EXTENDED BATTERY BANKS = 363 lbs. (165 kg) MAX. (EACH BANK)
7.If extended battery banks are to be connected to the UPS, please refer to page 7 for hardwire models and page 16 for all other models.
8.If unattended computer shutdown and monitoring are desired, connect the green UPS/Computer cable to the
9.Verify the location selected has adequate ventilation to allow for the proper cooling of the UPS.
DO NOT BLOCK UPS FANS OR AIR VENTS. THE UPS MUST NOT BE INSTALLED IN AN ENCLOSED AREA.
10.For further installation instructions covering hardwire models
11.Lower the leveling feet.
a.Verify the flooring at the UPS or battery bank installation location is rated for the weight of the equipment.
b.Roll the UPS or extended battery bank to the final installation location.
c.Locate the position of the (4) levelling feet underneath the UPS near its four corners. (see picture below).
d.Using your fingers and a 12mm open end wrench, screw the levelling feet in a clockwise direction, lowering the feet until all four feet are securely against the floor.
12.For further installation details covering the following models having a line cord and PDU, please refer to page 13. Models
Leveling Feet Adjustment
6