Maintenance Bypass Operating Instructions

Unless configured as a frequency converter, SG 5 & 6kVA models are equipped with an internal maintenance bypass switch. The switch is located on the rear panel of the UPS and is clearly identified, See page 15. The maintenance bypass switch is a manual second bypass primarily provided for service purposes and should not be confused with the internal UPS static bypass. It provides a means of changing the internal UPS batteries while maintaining power to the critical loads connected to the output of the UPS. It also can a provide method of supplying power to the critical load around the UPS electronics in the event of a hard UPS failure.

CAUTION

Improper use of the maintenance bypass switch will result in damage to the UPS.

The following procedures must be followed to assure proper UPS operation.

To place the UPS on Maintenance Bypass when the UPS is functioning normally perform the following:

1.Place the UPS into internal bypass by depressing the multi-function “ON.OFF” button located on the UPS front control panel. You can verify the UPS is in internal bypass as the yellow “BYPASS” light will be illuminated.

Note: The UPS must be in the internal bypass mode prior to performing the next step.

2.The Maintenance Bypass switch may now be turned clockwise to the “Bypass” position. The UPS is now operating directly from utility power.

When the UPS is off, the Maintenance Bypass switch may be turned to “Bypass” position and the input AC circuit breaker turned on to power the loads connected to the UPS output.

20

Image 22
Contents Owners Operating Manual Table of Contents SG Series ON-LINE UPS System Block Diagram Important Safety Instructions Electric, IncTrue Regenerative On-Line Design Input Power Factor CorrectionExtended Battery Bank Option Microprocessor ControlInstallation Instructions General Common for all modelsDisregard On Designation Leveling Feet Adjustment Model Output Requirements View of the Input/Output Hardwire Terminal BlockUPS Output Requirements Do not USE the Upper Terminal ConnectionsInternal UPS Diagram SG5K-2TC & SG6K-2TCInstallation Instructions SG5K-2TXC & SG6K-2TXCExtended Battery Bank Selection Guide USE Copper Conductors only Receptacle Model RequiredUPS Output Details Output Power Distribution Center Typical Power Distribution Center ConfigurationRefer to page 20 for Operating Instructions All models except hardwire Extended Battery Bank DC InterconnectionInstallation Procedure Line / Site Wiring Fault Indicator LED Load Level Indicator LEDsBattery Level Indicator LEDs Battery Mode Indicator LEDGreen Mode LED Indicator Bypass Indicator LEDInverter Indicator LED Over Crest Indicator LEDCategory one alarms Audible AlarmsCategory two alarms Page Location Communications InterfacesSupported Protocols DRY Contact & Opto Coupler Interface Board Options PIN Assignment for the Falcon Battery Life vs. Temperature Care & MaintenanceBattery Replacement Storing the UPS and Batteries FCC ConsiderationsSUPPORT@FALCONUPS.COM Technical SupportRequesting Technical Information or Support 800.842.6940 Falcon Web SupportWarranty General Provisions6kVA Models