Connection of Data and Telecommunications Cables

Data and telecommunication interfaces are classified according to their safety status.

The following table lists the status of several standard interfaces. If the status of a given port differs from the standard one, a notice will be given in the manual.

Ports

Safety Status

 

 

V.11, V.28, V.35, V.36, RS-530,

SELV Safety Extra Low Voltage:

X.21, 10 BaseT, 100 BaseT,

Ports which do not present a safety hazard. Usually

Unbalanced E1, E2, E3, STM, DS-2,

up to 30 VAC or 60 VDC.

DS-3, S-Interface ISDN, Analog voice

 

E&M

 

xDSL (without feeding voltage), Balanced E1, T1, Sub E1/T1

TNV-1 Telecommunication Network Voltage-1:

Ports whose normal operating voltage is within the limits of SELV, on which overvoltages from telecommunications networks are possible.

FXS (Foreign Exchange Subscriber)

TNV-2

Telecommunication Network Voltage-2:

 

 

Ports whose normal operating voltage exceeds the

 

 

limits of SELV (usually up to 120 VDC or telephone

 

 

ringing voltages), on which overvoltages from

 

 

telecommunication networks are not possible. These

 

 

ports are not permitted to be directly connected to

 

 

external telephone and data lines.

 

 

 

FXO (Foreign Exchange Office), xDSL

TNV-3

Telecommunication Network Voltage-3:

(with feeding voltage), U-Interface

 

Ports whose normal operating voltage exceeds the

ISDN

 

 

limits of SELV (usually up to 120 VDC or telephone

 

 

 

 

ringing voltages), on which overvoltages from

 

 

telecommunication networks are possible.

 

 

 

Always connect a given port to a port of the same safety status. If in doubt, seek the assistance of a qualified safety engineer.

Always make sure that the equipment is grounded before connecting telecommunication cables. Do not disconnect the ground connection before disconnecting all telecommunications cables.

Some SELV and non-SELV circuits use the same connectors. Use caution when connecting cables. Extra caution should be exercised during thunderstorms.

When using shielded or coaxial cables, verify that there is a good ground connection at both ends. The earthing and bonding of the ground connections should comply with the local codes.

The telecommunication wiring in the building may be damaged or present a fire hazard in case of contact between exposed external wires and the AC power lines. In order to reduce the risk, there are restrictions on the diameter of wires in the telecom cables, between the equipment and the mating connectors.

Order from: Cutter Networks

Ph:727-398-5252/Fax:727-397-9610

www.bestdatasource.com

Image 7
Contents RIC-E1 Order from Cutter Networks Ph727-398-5252/Fax727-397-9610 International Headquarters RAD Data Communications Inc RIC-E1Limited Warranty Please observe the following precautions General Safety InstructionsConnection of AC Mains General Safety PracticesConnection of DC Mains Isdn Ports Safety StatusElectromagnetic Compatibility EMC Canadian Emission Requirements Supplementary Information SafetyManufacturers Name Manufacturers Address Product NamesQuick Start Guide Installing RIC-E1Setting the Internal Jumpers Jumper Description Values Default SettingOperating RIC-E1 Connecting the CablesTo connect cables Contents List of Figures Versions Power SupplyChapter Introduction OverviewApplication Physical DescriptionTiming Reference Functional Block DiagramDiagnostics Functional DescriptionInternal oscillator Technical SpecificationsReceive, derived from the received signal Derived from three alternative sourcesEnvironment DiagnosticsPower PhysicalTechnical Specifications Package Contents Chapter Installation and SetupSite Requirements and Prerequisites To set the jumpers Configuring RIC-E1Setting the Jumpers To install RIC-E1RIC-E1 Jumper Locations RIC-E1 Jumper Settings Closing the RIC-E1 Case Connecting the InterfacesConnecting the E1 Line Selecting the ImpedanceConnecting the DC Power Connecting the PowerConnecting the DTE Connecting the AC PowerInstallation and Setup Chapter Operation Front Panel IndicatorsDesignation Color Function Turning Off Operating InstructionsTurning On Operating RIC-E1Performing Local Analog Loopback Chapter Troubleshooting DiagnosticsActivating Local Analog Loopback To activate the local analog loopback from RIC-E1/R TroubleshootingRIC-E1 Troubleshooting Deactivating Local Analog LoopbackTechnical Support Technical Support ASM-MN-214 Card Cage Line ConnectorDTE Connector Chapter RIC-E1/R CardASM-MN-214 Rear Panel DC Supply Power SupplyPower Supply with Redundancy AC SupplyIR-ETH or IR-ETH RIC-E1/R Front PanelASM-MN-214 Front Panel Setting Internal Jumpers and Switches Installing the RIC-E1/R CardRIC-E1/R PCB Layout RIC-E1/R Jumper Settings To install the RIC-E1/R card in the ASM-MN-214 card cage Installing RIC-E1/R into the ASM-MN-214 Card CageRIC-E1/R Card V.35, X.21 and RS-530 Interface Connectors Appendix a Interface Connector WiringSignal Function 36, 37-Pin RS-530, 25-pin Circuit V.36 Interface ConnectorPin Function Line Interface ConnectorTable A-3. RJ-45 Line Interface Connector, Pin Assignment Signal Function 36, 37-pin RS-530, 25-pin Pin CircuitAppendix a Interface Connector Wiring Appendix B IR-ETH Interface Module ContentsIntroduction Table B-1. RJ-45 Pinout IR-ETH OptionsStandalone RIC-E1 RIC-E1/R CardFigure B-3. RIC-E1/R with IR-ETH Installation and Operation LED Indicators Setting the DIP SwitchTable B-2. DIP Switch Settings ACT Connecting the LANTable B-4. IR-ETH LED Indicators, RIC-E1/R LinkAppendix C IR-ETH/V Interface Module IR-ETH/V Options RIC-E1 Data 00, 01, 02, … For example, MDI in OFF position, MDI is enabledMbps full duplex, 285 ∝s ThroughputSection Name Description Possible Settings Factory Setting Setting the DIP SwitchesTable C-2. DIP SW1 Switch Settings Moved by the user Table C-3. DIP Switch SW2 SettingsBackpressure and Flow Control Table C-4. IR-ETH/V LED IndicatorsColor Function Introduction Appendix D IR-IP Interface ModuleAppendix D IR-IP Interface Module Frame Relay RFC Connector 10BaseT Shielded RJ-45Standard Ieee 802.3/Ethernet Data Rate ProtocolsRIC-E1/ IP Table D-2. IR-IP LEDs Functions RIC-E1/R Card IR-IP LEDsIR-IP Controls Table D-1. IR-IP LEDs Functions Standalone RIC-E1Table D-4 RJ-45 Pinout Control Function Values Default SettingIR-IP Management Subsystem, General Table D-3. IR-IP ControlsDefault IP Communication Parameters Accessing the IR-IP Management SubsystemTo allow the IR-IP configuration Performing Preliminary ConfigurationRescue Configuration Outline of Preliminary ConfigurationIP Learning Mechanism Connecting the Telnet HostPreliminary Telnet Host Configuration Assigning the Router LAN Interface AddressTo configure the IP router LAN address To view and edit the ARP table contentsAssigning a LAN IP Address to a New IR-IP No ping replies from IR-IP Changing the LAN IP Address of a Configured IR-IPAfter RIC-E1 is turned on, the ERR indicator does not light What to Do IfIR-IP Management Utility General Operating ProceduresStarting a Management Utility To access the Quick Setup menu Quick Setup MenuMenu Structure of Management Utility WAN IP Address Default GatewayLAN IP Address LAN IP MaskDhcp Relay Read Protocol from DIP SwitchesOperation with Default Gateway To configure the IR-IP as a Dhcp relayProtocol Management Access MenuTelnet Password To access the Management Access menuTo access the Device Identification menu Advanced Setup MenuTelnet Inactivity Timeout To access the Advanced Setup menuContact Person To access the Interface Parameters menuInterface Parameters Menu Device NameWAN Protocol Parameters Frame Relay Protocol Menu Protocol Field Compression Authentication ProtocolWAN Protocol Parameters PPP Protocol Header and Control Field CompressionMulticast IP Figure D-17. Multicast IP Menu Multicast ForwardingDevice Control To access the Device Control menuStatic Groups New Software Download Menu Viewing Error Log ScreenResetting the LAN Interface Erasing ConfigurationResets Menu Resetting the DeviceView Menu Configuration and ConnectionTo access the View menu To access the Configuration and Connection screenARP Tables To access the ARP Tables screenDisplaying Statistics To access the Multicast Groups Table screenTo access the Statistics menu Multicast Groups Table ScreenTo access the Diagnostic Tools menu Diagnostic Tools Ping TerminalTo ping a host Using the Ping FunctionDesired positions, and then turn the RIC-E1 on again Erasing User’s ConfigurationTo erase the user’s configuration Erasing IR-IP SoftwareCase, it is recommended to turn RIC-E1 off and then back on Erasing Application SoftwareDownloading New Software To erase the application softwareAppendix D IR-IP Interface Module Rear Panel Appendix E IR-X.21B Interface ModuleSelecting the IR-X.21B Timing EXT Clock ModeIR-X.21B INT/LBT Clock ModeBuffer Appendix E IR-X.21B Interface Module IR-ETH Impedance, 2-4IndicatorsIndex IP-IRLED IR-IPRequirements, 2-1RIC-E1/R Card Excellent Good Fair Poor Very Poor Customer Response FormError Report Order from Cutter Networks Ph727-398-5252/Fax727-397-9610 International Headquarters