Installation
System Wiring
NOTICE
Do not connect any of the SW+ (13,9,5,1) and SW- (16,12,8,4) pins together, either directly or via a switch closure. Doing so will create a short circuit condition which will disable and potentially damage the controller.
NOTE: On an AC controller (p/n 24B596), the J7 strip is line (input) voltage but the J6 strip is all 24VDC. On a DC controller (p/n 24B59‘), the J6 and J7 terminals all carry the input voltage.
Input Sensor Wiring:
DRY CONTACT SWITCH | SINK SWITCH - 2 or 3 Wire Type |
J6 | J6 |
4 (SW
3 (SEN (x))
2 (IN (x))
1 (SW +) x = sensor input 1,2,3 or 4
4 (SW
3 (SEN (x))
2 (IN (x))
1 (SW +)
FIG. 8
FIG. 10
SOURCE SWITCH - 2 or 3 Wire Type
x = sensor input 1,2,3 or 4
J6
4 (SW
3 (SEN (x))
2 (IN (x))
1 (SW +)
x = sensor input 1,2,3 or 4
FIG. 9
313855H | 11 |