Graco 24B591, 24B596 Pump On Ended with Cycle Switch Activation, Pump Off Ended with Time

Page 31

Pump On Ended with Cycle Switch Activation

A B

C D

E

FIG. 58

If the Pump On sequence has been programmed to end by a Cycle Switch Activation:

The GLC 4400 pump output relay activates (J7-3) and will stay on until the correct number of cycle switch closures is received (J6-3) (see Setup Menus, Cycle End Setup page 19).

The Pump On LED (A) remains on during this time.

The Pump On (C) icon displays.

The Cycle LED (B) and Cycle Count Mode icon (D) display indicating the cycle switch is activated.

The cycle indicator bar (E) displays a visual repre- sentation of the cycle switch closures received.

If the set number of cycle switch closures is not received before time expires, an alarm occurs.

Run Mode

Pump Off Ended with Time

D

A

C

FIG. 59

If the Pump Off sequence has been programmed to be ended by TIME:

The GLC 4400 pump output relay activates (J7-3) and will stay off until the time expires. (see Setup Menus, Pump Off, page 20).

The Pump On LED (A) remains off during this time.

The Pump Off icon (C) displays.

The Timer Mode icon (D) displays and indicates the Timer Mode.

Pump Off Ended with Machine Counts

B

A

CD

FIG. 60

If the Pump Off sequence has been programmed to be ended by MACHINE COUNTS:

313855H

31

Image 31
Contents GLC Lubrication Controller Important Safety InstructionsElectric Shock Hazard Direction Arrows Run Mode FunctionsComponent Identification Keypad, Display, and IconsIcons Typical Installation InstallationGrounding Installing the Lubrication ControllerOptional I/O Wiring Diagrams System Configuration and WiringSystem Configurations Modes of Operation Sensor Wiring ConfigurationsDivider Valve System System ConfigurationDual Line System Injector System Input Sensor Wiring System WiringSource Switch 2 or 3 Wire Type 30VDC Pump on = Time Pump OFF = TimePump on = Cycle or Pressure Pump OFF = Time Dry Contact, shown. For other configuration, see or FIGPump on = Cycle or Pressure Pump OFF = Machine Count System Wiring Options 30VDC System Wiring Options Alarm Out100/240VAC System Setup PIN Mode Enabled SetupSee Electric Connection Warning, Main Screen System SetupPump on Setup Timer SetupCycle END Setup Pressure SetupCycle Mode Selection Pump OFF SetupTo Set the Pump OFF Option If Count is selected If Time is selectedIf Both is selected Power Up can be programmed one of four ways Power UP SetupThird At Power Up, immediately go to Pump on normal on time Pulsed Pump Screen Pulsed SetupTo enable PIN Code Entry PIN SetupQuick Cycle Setup Display SetupDisplay Backlight Quick Cycle Screen Setup LOW Level Filtering SetupLow Level Filtering Screen Setup Screen Identification Run ModePump On Ended with Pressure Prelube Power UpPump On Ended with Time Pump Off Ended with Time Pump On Ended with Cycle Switch ActivationPump Off Ended with Machine Counts Pump Off Ended with Machine Counts Max Time Entered Alarms ScreenModes of Operation TroubleshootingProgram Settings Description Problem SolutionIP69K Technical DataMounting Hole Layout DimensionsGraco Information Graco Standard Warranty