Graco 24B591, 24B596 LOW Level Filtering Setup, Quick Cycle Screen Setup

Page 27

Quick Cycle Screen Setup

The Quick Cycle screen setup is used to setup a Trou- bleshooting profile.

FIG. 50

1.Use the Arrow keys to move the cursor over the CYCLES field.

2.Press ENTER.

3.Use the UP/DOWN arrows to move up and down through the numbers 0-9 until the first number you want in the CYCLES field is displayed.

4.Use the RIGHT arrow to move the cursor to the next field. Repeat step 3.

NOTE: The maximum number of Cycles you can setup in this field is 99.

5.Use the Arrow keys to move the cursor over the TIME ON field.

6.Press ENTER.

NOTE: Time On and Time Off in QUICK CYCLE mode only, are displayed in Seconds.

7.Use the UP/DOWN arrows to move up and down through the numbers 0-9 until the first number you want to use in the TIME ON field is displayed in the field.

8.Use the RIGHT arrow to move the cursor to the next field. Repeat step 7.

9.Press ENTER.

10.Use the Arrow keys to move the cursor over the TIME ON field.

11.Press ENTER.

Setup

12.Repeat steps 7 - 9 for the TIME OFF field.

13.Use the Arrow keys to move the cursor over the pull-down menu.

14.Select ON.

15.The Quick Cycle begins.

NOTE:

The maximum Time Off and Time On is 99 seconds.

When complete, the system returns to the Run Mode. It does not come back to the Quick Cycle Setup Screen.

LOW LEVEL FILTERING Setup

FIG. 51

1.Use the UP/DOWN Arrow keys to move the cursor over LL FILTERING.

2.Press ENTER to display the LL FILTERING setup screen.

313855H

27

Image 27
Contents GLC Lubrication Controller Important Safety InstructionsElectric Shock Hazard Direction Arrows Run Mode FunctionsComponent Identification Keypad, Display, and IconsIcons Typical Installation InstallationGrounding Installing the Lubrication ControllerOptional I/O Wiring Diagrams System Configuration and WiringSystem Configurations Modes of Operation Sensor Wiring ConfigurationsDivider Valve System System ConfigurationDual Line System Injector System System Wiring Input Sensor WiringSource Switch 2 or 3 Wire Type 30VDC Pump on = Time Pump OFF = TimePump on = Cycle or Pressure Pump OFF = Time Dry Contact, shown. For other configuration, see or FIGPump on = Cycle or Pressure Pump OFF = Machine Count System Wiring Options System Wiring Options Alarm Out 30VDC100/240VAC Setup System Setup PIN Mode EnabledSee Electric Connection Warning, Main Screen System SetupPump on Setup Timer SetupCycle END Setup Pressure SetupPump OFF Setup Cycle Mode SelectionTo Set the Pump OFF Option If Time is selected If Count is selectedIf Both is selected Power Up can be programmed one of four ways Power UP SetupThird At Power Up, immediately go to Pump on normal on time Pulsed Pump Screen Pulsed SetupTo enable PIN Code Entry PIN SetupDisplay Setup Quick Cycle SetupDisplay Backlight Quick Cycle Screen Setup LOW Level Filtering SetupLow Level Filtering Screen Setup Screen Identification Run ModePrelube Power Up Pump On Ended with PressurePump On Ended with Time Pump On Ended with Cycle Switch Activation Pump Off Ended with TimePump Off Ended with Machine Counts Pump Off Ended with Machine Counts Max Time Entered Alarms ScreenModes of Operation TroubleshootingProgram Settings Description Problem SolutionIP69K Technical DataMounting Hole Layout DimensionsGraco Information Graco Standard Warranty