Troubleshooting

Troubleshooting

Description

Problem

Solution

 

 

 

 

 

 

 

 

Power light off: Timer is not receiving

 

 

power. Verify connections and verify

 

No power supplied to solenoid

power supply.

Timer fails to activate solenoid

 

Power light on: Verify solenoid con-

 

nections

 

 

 

 

 

 

Solenoid faulty

Replace solenoid

 

 

 

 

Timer faulty

Replace timer

 

 

 

 

Low level or other alarm

Refill reservoir

 

 

 

Pressure switch fails to shut down

Pressure switch incorrectly wired

Verify proper connections

 

 

Pressure switch faulty

Replace pressure switch

system

 

 

Timer faulty

Replace timer

 

 

 

 

Program Settings

 

Modes of Operation

Description

Maximum / Minimum and Additional Comments

 

 

 

 

TIMER Setup, page 18

HH:MM:SS (00:00:01 - 99:59:59)

 

 

PRESSURE Setup, page 19

HH:MM:SS (00:00:01 - 99:59:59)

 

 

CYCLE END Setup, page 19

HH:MM:SS (00:00:01 - 99:59:59)

 

 

CYCLE MODE Selection, page 20

Cycles = 01 - 99

 

 

 

Time, Pressure or Cycles

PUMP ON Setup, page 18

Pump ON Time: HH:MM:SS (00:00:01 - 99:59:59)

 

Cycles: 01 - 99 (only used when mode of operation = cycles)

 

 

 

Time, Count or Both

PUMP OFF Setup, page 20

Pump OFF Time: HH:MM:SS. (00:00:01 - 99:59:59)

 

Count: 01 - 9999

 

 

POWER UP Setup, page 22

MM:SS (00:01 - 59:59)

 

 

PULSED Output (pump), page 24

Maximum Time OFF and Time ON: SS (01-99)

 

 

PIN Number Setup, page 25

ON / OFF

0000 - 9999

 

 

 

 

Cycles = 01 - 99

QUICK CYCLE SCREEN Setup, page 26

Time ON and Time OFF: SS (01-99)

 

Execute: YES / NO

 

 

 

YES / NO

PRELUBE on Power Up, page 30

Delay: YES / NO

 

TIME: MM:SS (00:01 - 59:59)

 

 

313855H

33

Image 33
Contents GLC Lubrication Controller Important Safety InstructionsElectric Shock Hazard Component Identification Run Mode FunctionsKeypad, Display, and Icons Direction ArrowsIcons Typical Installation InstallationGrounding Installing the Lubrication ControllerSystem Configurations Modes of Operation System Configuration and WiringSensor Wiring Configurations Optional I/O Wiring DiagramsDivider Valve System System ConfigurationDual Line System Injector System System Wiring Input Sensor WiringSource Switch 2 or 3 Wire Type 30VDC Pump on = Time Pump OFF = TimePump on = Cycle or Pressure Pump OFF = Time Dry Contact, shown. For other configuration, see or FIGPump on = Cycle or Pressure Pump OFF = Machine Count System Wiring Options System Wiring Options Alarm Out 30VDC100/240VAC Setup System Setup PIN Mode EnabledSee Electric Connection Warning, Pump on Setup System SetupTimer Setup Main ScreenCycle END Setup Pressure SetupPump OFF Setup Cycle Mode SelectionTo Set the Pump OFF Option If Time is selected If Count is selectedIf Both is selected Power Up can be programmed one of four ways Power UP SetupThird At Power Up, immediately go to Pump on normal on time Pulsed Pump Screen Pulsed SetupTo enable PIN Code Entry PIN SetupDisplay Setup Quick Cycle SetupDisplay Backlight Quick Cycle Screen Setup LOW Level Filtering SetupLow Level Filtering Screen Setup Screen Identification Run ModePrelube Power Up Pump On Ended with PressurePump On Ended with Time Pump On Ended with Cycle Switch Activation Pump Off Ended with TimePump Off Ended with Machine Counts Pump Off Ended with Machine Counts Max Time Entered Alarms ScreenProgram Settings TroubleshootingDescription Problem Solution Modes of OperationIP69K Technical DataMounting Hole Layout DimensionsGraco Information Graco Standard Warranty