Connecting the server to power 41
A qualified electrician must implement the single-point ground reference as required among the power outlets of the CallPilot server, its associated peripherals, and the power outlets of the switch.
Provide a sufficient number of properly grounded power outlets or power bars for all equipment.
The single-point ground (SPG) required by the system can be an isolated ground (IG) bus or AC equipment ground (ACEG) bus in the service panel or transformer. The system must be connected to safety ground or protective earth in accordance with NEC requirements. For international use, the system must be connected to safety ground or protective earth in accordance with Paragraph 2.5 of EN60950/IEC950.
Note: For a complete description of approved ground sources and
methods, seeCommunication Server 1000M and Meridian 1: Large System Planning and Engineering (NN43021-220). Insulated ground wire must be used for system grounding.
Before you connect the server to the power source, review the following diagram and the warning that follows to ensure that all peripheral hardware devices are in place.
Nortel CallPilot
600r Server Hardware Installation
NN44200-307 01.03 Standard
5.014 May 2008
Copyright © 2007-2008, Nortel Networks