Panamax MB1000 manual Operating Modes

Page 6

Operating Modes

Normal Operation (Utility Power) Mode

When connected to a live power source, the MB1000 provides power and is ready to provide protection from under- and over- voltages.

Normal Operation Screen

120 VOLTS

NORMAL POWER

SETUP

Rotate the navigation dial to scroll through the screens.

Automatic Voltage Regulation (AVR) Mode

Sensitive AVR: when receiving input voltages of 98 VAC – 135 VAC, the MB1000 supplies a regulated voltage of 120 VAC ± 5 VAC.

Standard AVR: when receiving input voltages of 93 VAC – 145 VAC, the MB1000 supplies a regulated voltage of 120 VAC ± 10 VAC.

OFF: AVR is disabled. No voltage correction.

UPS Mode

In the event of a loss of power to the unit, over-voltage, or under-voltage, the MB1000 will function as a battery back-up. An audible alarm will sound and the display will indicate the fault as well as the number of minutes of battery life remaining.

UPS Mode Screen

FAULT

BATTERY: 15 MIN

Setup Mode

The setup menu allows the user to adjust several of the operating parameters of the unit.

Please refer to diagram (page 5) for a detailed map of the menu structure.

Setup Menu Navigation

Clockwise (CW) rotation of the navigation dial advances the menu to the next item. If the menu is at the last item, SYSTEM INFO, return to Normal Operation Mode.

Counter clockwise (CCW) rotation of the navigation dial sends the menu to the previous item. If the menu is at the first item, DISPLAY BRIGHTNESS, return to Normal Operation Mode.

Pressing the navigation dial selects the current menu item.

If there is no activity of the navigation dial for 60 seconds, the menu will automatically return to Normal Operation Mode.

Parameter Selection and Adjustment

CW rotation of the navigation dial INCREASES the selected parameter, or advances to the NEXT available value.

CCW rotation of the navigation dial DECREASES the selected parameter, or goes back to the PREVIOUS value. Pressing the navigation dial selects the current parameter value.

If there is no activity of the navigation dial for 60 seconds, return to Normal Operation Mode.

If the BACK parameter is selected, return to the menu item selec- tion.

Display Brightness

Display Brightness adjusts the brightness of the display back- light.

Display Scroll Mode

If enabled, the display will automatically advance to the next screen every 5 or 10 seconds.

Display Sleep Mode

With Display Sleep Mode enabled, the Display will go to the lowest brightness setting (25%) after the designated time of inactivity of the Navigation Dial {30 SEC, 60 SEC }.

The display will return to the set brightness level upon entering Setup Mode, or UPS Mode.

4

Image 6
Contents Features MB1000 InstructionsTable of Contents Before You Begin Unpacking Inspect the UPS upon receipt Important Safety Instructions Battery replacement recommended every two yearsInput Installing Your UPSAC Power UPS OutputPower Switch Basic Operation Front Panel DescriptionOperating Modes Setup Mode Flowchart Advanced Operation RS-232 Control with Open Protocol RS-232 Communications Protocol & Command SetTo program IR output RS-232 serial interface can be used in the following waysALL on Controller CommandsCommunications Protocol ALL OFFSwitch Outlet Bank SET Buzzer ModeSET Bank 2 Threshold SET Linefeed Mode SET AVR ModeSET Feedback Mode SET Display Sleep ModeQueries Identify Reset Factory SettingsPower Status Outlet StatusPower Button Status Change Condition Response Battery Level StatusList Configuration Power Fault Status Change Condition ResponseLimited Product Warranty FCC Notice and WarrantiesCaractéristiques Table des matières Avant de commencerUn câble USB Les dispositifs fournis par PF Power ne sont pas destinés Ne tentez pas le remplacement de la batteriePour votre sécurité Alimentation c. a Installation de votre onduleurAlimentation Sortie onduleurManœuvres de base Description DU Panneau Frontal InterrupteurModes de fonctionnement IR1 Test IR1 Program IR1 Sample Fail Manœuvres complexes Protocole de communication et jeu de commandes RS-232 Pour programmer les émissions infrarougesContrôle RS-232 avec protocole libre Activation Générale Commandes de contrôleProtocole de communication Désactivation GénéraleConfigurer LE Seuil Plancher DU Bloc Configurer LE Mode DE Signal D’ALARMEBasculer UN Bloc DE Prises Configurer LE Mode Saut DE Ligne Configurer LE Mode DE Régulation Automatique DE LA TensionConfigurer LE Mode DE Réponse Configurer LA LuminositéÉtat DU Courant Requêtes IdentificationÉtat DES Prises TensionsChangement D’ÉTAT DE L’INTERRUPTEUR Condition Réponse Liste DES ConfigurationsCharge DE LA Batterie Changement D’ÉTAT DU Courant Condition RéponseAvis FCC et garanties AvertissementMB1000 Instrucciones CaracterísticasTabla de contenido Págs , 9, 10, 11Cable USB Instrucciones de seguridad importantes ¡IMPORTANTECorriente alterna Instalación del suministro de energía ininterrumpible UPSEntrada Salida de UPSOperación básica Descripción DEL Panel Frontal Infrarroja IRModos de operación IR1 Test IR1 Program IR1 Sample Fail Operación avanzada Protocolo de comunicaciones RS-232 y conjunto de comandos Para programar la salida IREncender Todo Protocolo de comunicacionesComandos del controlador Apagar TodoConfigurar Umbral DE Regleta Configurar Modo DE ZumbadorConmutar Regleta Configurar Modo DE Salto DE Línea Configurar Modo AVRConfigurar Modo DE Realimentación Configurar Brillo DEL MedidorEstado DE Alimentación Consultas IdentificaciónEstado DE Regletas VoltajeCambio DE Estado DE Regleta Listar ConfiguraciónEstado DE Nivel DE Batería Condition ResponseNotificación de la FCC y garantías Notificación de la FCCGarantía de dos años de la batería