APC Power Supply manual Install a circuit breaker, Torque specifications and tools required

Page 23

Installation Procedures: Connect the Power Source to the PDU

Install a circuit breaker

Make sure the cables used for power input are sufficiently protected by a appropriately-rated circuit breaker. See “Electrical Requirements and Specifications” on page 8.

Route the input conductors to the main input circuit switch

1.Route the input conductors to the main input circuit switch of the PDU, as follows:

For overhead wiring, run the input conductors directly to the main input switch.

For wiring under a raised floor, run the input conductors through

the wireway (,) within the PDU to the main input switch.

,

Torque specifications and tools required

Before connecting to the terminals, verify the torque specifications below by checking the specifications on the main input switch.

Terminal

Torque

Tools

L1, L2, L3

200V input: 8–13N·m

6-mm Allen wrench

 

 

415V input: 5–7 N·m

#3 Plus Driver

 

 

 

PE

14N·m

3/16-mm Allen wrench

 

 

 

InfraStruXure Site Planning, Installation, Start-Up

15

Image 23
Contents InfraStruXure Installation and Start-Up This manual is available in English on the enclosed CD About this Manual Page Contents Start-Up Procedure Configuration Page Overview SafetySafety symbols used in this manual Cross-reference symbols used in this manualRegister equipment with the fire department Installation/MaintenanceTotal power off procedure Input Voltage Circuit Breaker SizeNetShelter VX Seismic Enclosure DimensionsSite Preparation InfraStruXure PDUNetShelter VX Enclosure Space Considerations Component Maximum Unpacked Maximum Packaged Weight ConsiderationsInfraStruXure PDU Heat Output Heat Output200V Input 415V Input Electrical Requirements and SpecificationsProcedures requiring a licensed electrician Electrical requirementsBasic Installation Procedure Licensed electrician must connect the power source Bolt Enclosures to the Floor Installation ProceduresJoin Adjacent Enclosures and Bolt Enclosures to the Floor Join adjacent enclosuresEnsure Total Power Off Attach conduit to the PDU for the input conductors Connect the Power Source to the PDUAccess the PDU Main Input switch Installation Procedures Connect the Power Source to the PDU Terminal Torque Tools Install a circuit breakerRoute the input conductors to the main input circuit switch Torque specifications and tools requiredConnect input conductors Overview Output relay specificationsHow to connect contacts to the PDU Monitoring Unit InfraStruXure Site Planning, Installation, Start-Up Cable Ladders for overhead wiring across rows Install the InfraStruXure Manager and Hub or Switch Install InfraStruXure Rack-Mount DevicesInstall the Rack Automatic Transfer Switches ATS Install the Rack Power Distribution Units PDURoute and attach power cables to equipment racks Route and Attach Overhead WiringInstallation Procedures Route and Attach Overhead Wiring Installation Procedures Route and Attach Overhead Wiring Wiring Under the Floor Alternative Installation Procedures Wiring Under the Floor Alternative Connect network cables to InfraStruXure components Route Data Cables to the InfraStruXure Manager Hub or SwitchOverhead routing Ensure that all power is off Start-Up ProcedureSafety warnings Apply power to the system Start-Up Procedure InfraStruXure System Page Configure the InfraStruXure Manager ConfigurationPage Appendix A-System Operation How to Apply Power to the SystemHow to Ensure Total Power Off Page APC Worldwide Customer Support