Site Preparation
Installation Space Requirements
Clearance for 20.59 in/523 mm Enclosures
(A)
(B)
UPS |
|
|
|
| Conduit Box |
| |
| (F) |
|
|
(C) | (D) |
|
|
| (G) |
|
|
(E) |
|
|
|
|
|
|
|
Space requirements |
| in | mm |
|
|
|
|
Minimum clearance above Enclosure (A) |
| 20.00 | 508 |
|
|
|
|
Enclosure depth (B) |
| 32.99 | 838 |
|
|
|
|
Enclosure width (C) |
| 20.59 | 523 |
|
|
| |
Minimum rear service clearance* (compliant with NEC 110.26 for | 36.00 | 914 | |
North America) (D) |
|
|
|
|
|
|
|
Minimum front clearance (E) |
| 40.00 | 1,000 |
|
|
|
|
Conduit Box, depth (F) |
| 3.46 | 88 |
|
|
| |
No side clearance required (add width of Stabilizing Brackets for | 0 | 0 | |
floor anchoring if applicable) |
|
|
|
|
|
|
|
Stabilizing Bracket width |
| 3.34 | 85 |
|
|
| |
Total installation depth, inclusive of Front Panel, Conduit Box and | 112.45 | 2,840 | |
minimum front and rear clearances (G) |
|
|
|
|
|
|
|
*) Minimum free rear space for ventilation 4 in/100 mm.
10 |