Site Preparation – Operating Environment
Recommended current protection
AC output
Note
Dual/single |
|
|
|
|
|
|
mains | Connection | 10 kVA | 15 kVA | 20 kVA | 30 kVA | Notes |
configuration | ||||||
|
|
|
|
|
|
|
Single | Mains/bypass | 35 A | 60 A | 80 A breaker | 125 A breaker |
|
| input | breaker (30 | breaker (30 | (30 kAIC) | (30 kAIC) |
|
|
| kAIC) | kAIC) |
|
|
|
|
|
|
|
|
|
|
Dual | Mains input | 35 A | 60 A | 80 A breaker | 125 A breaker | 1, 2 |
|
| breaker | breaker | (30 kAIC) | (30 kAIC) |
|
|
| (30 kAIC) | (30 kAIC) |
|
|
|
|
|
|
|
|
|
|
Dual | Bypass input | 35 A | 60 A | 80 A breaker | 125 A breaker | 1, 2 |
|
| breaker | breaker | (30 kAIC) | (30 kAIC) |
|
|
| (30 kAIC) | (30 kAIC) |
|
|
|
|
|
|
|
|
|
|
Any | Output | 35 A fast- | 60 A fast- | 80 A fast- | 125 A fast- | 3, 4 |
|
| acting class | acting class | acting class | acting class |
|
|
| J fuse | J fuse | J fuse | J fuse |
|
|
|
|
|
|
|
|
Note 1: If the available fault current of the installation is below 30 kA, a lower
Note 2: For breaker settings, refer to below table listing available overload currents.
Note 3: If the available fault current of the installation is less than 1200 A for the 10 kVA and 15 kVA UPS sizes, and below 2300 A for the 20 kVA and 30 kVA UPS sizes, a breaker (of the same value as for the bypass input) can be used.
Note 4: Recommended maximum rating of a
Minimum breaker settings for 10 kVA UPS
Overload Event | Mains input | Bypass input | Output | Duration | Notes |
|
|
|
|
|
|
Internal fault | 2 kA | 1.7 kA | 14 kA | <10 ms | 1 |
|
|
|
|
|
|
800% overload bypass | – | 223 A | 223 A | 500 ms |
|
operation |
|
|
|
|
|
|
|
|
|
|
|
150% overload normal/ | – | – | 42 A | 30 s |
|
battery operation |
|
|
|
|
|
|
|
|
|
|
|
125% overload normal/ | – | – | 35 A | 60 s |
|
battery operation |
|
|
|
|
|
|
|
|
|
|
|
Continuously | 34 A | 31 A | 31 A | ∞ |
|
|
|
|
|
|
|
Note 1: For the output value, the