Site Preparation – Operating Environment
Minimum breaker settings for 15 kVA UPS
Overload Event | Mains input | Bypass input | Output | Duration | Notes |
|
|
|
|
|
|
Internal fault | 2.5 kA | 2.1 kA | 14 kA | <10 ms | 1 |
|
|
|
|
|
|
800% overload bypass | – | 333 A | 333 A | 500 ms |
|
operation |
|
|
|
|
|
|
|
|
|
|
|
150% overload normal/ | – | – | 63 A | 30 s |
|
battery operation |
|
|
|
|
|
|
|
|
|
|
|
125% overload normal/ | – | – | 52 A | 60 s |
|
battery operation |
|
|
|
|
|
|
|
|
|
|
|
Continuously | 51 A | 46 A | 46 A | ∞ |
|
|
|
|
|
|
|
Note 1: For the output value, the
Minimum breaker settings for 20 kVA UPS
Overload Event | Mains input | Bypass input | Output | Duration | Notes |
|
|
|
|
|
|
Internal fault | 4 kA | 3.4 kA | 14 kA | <10 ms | 1 |
|
|
|
|
|
|
800% overload bypass | – | 444 A | 444 A | 500 ms |
|
operation |
|
|
|
|
|
|
|
|
|
|
|
150% overload normal/ | – | – | 84 A | 30 s |
|
battery operation |
|
|
|
|
|
|
|
|
|
|
|
125% overload normal/ | – | – | 70 A | 60 s |
|
battery operation |
|
|
|
|
|
|
|
|
|
|
|
Continuously | 68 A | 62 A | 62 A | ∞ |
|
|
|
|
|
|
|
Note 1: For the output value, the
Minimum setting of breakers for 30 kVA UPS
Overload Event | Mains input | Bypass input | Output | Duration | Notes |
|
|
|
|
|
|
Internal fault | 5 kA | 4.2 kA | 14 kA | <10 ms | 1 |
|
|
|
|
|
|
800% overload bypass | – | 667 A | 667 A | 500 ms |
|
operation |
|
|
|
|
|
|
|
|
|
|
|
150% overload normal/battery | – | – | 125 A | 30 s |
|
operation |
|
|
|
|
|
|
|
|
|
|
|
125% overload normal/battery | – | – | 105 A | 60 s |
|
operation |
|
|
|
|
|
|
|
|
|
|
|
Continuously | 102 A | 92 A | 92 A | ∞ |
|
|
|
|
|
|
|
Note 1: For the output value, the
14 |