Electrical Installation –
UPS ratings 220 V | 10 kVA | 15 kVA | 20kVA | 30 kVA | |
8 kW | 12 kW | 16 kW | 24 kW | ||
| |||||
|
|
|
|
| |
Input voltage / Bypass voltage (V) | |||||
| 220Y/ | 220Y/ | 220Y/ | 220Y/ | |
| 127 V | 127 V | 127 V | 127 V | |
|
|
|
|
| |
Input current (nominal, per phase) (A) | 22.9 | 34.6 | 46.5 | 68.9 | |
|
|
|
|
| |
Maximum input current per phase (continuous, at | 25.2 | 38.0 | 50.1 | 75.8 | |
minimum mains voltage) |
|
|
|
| |
|
|
|
|
| |
Input current protection for mains source or single | 3x35 | 3x60 | 3x80 | 3x125 | |
mains supply (external to UPS, not supplied) (A) |
|
|
|
| |
|
|
|
|
| |
Input current protection for bypass source in dual mains | 35 | 60 | 80 | 125 | |
configuration (external to UPS, not supplied) (A) |
|
|
|
| |
|
|
|
|
| |
Input frequency (Hz) range | |||||
|
|
|
|
| |
Output voltage (on line). (V) | 127/220 | 127/220 | 127/220 | 127/220 | |
Minimum and maximum values (+/- 1%) |
|
|
|
| |
|
|
|
|
| |
Output current (nominal, per phase) (A) | 26.2 | 39.4 | 52.5 | 78.7 | |
|
|
|
|
| |
Maximum output current | 28.9 | 43.3 | 57.7 | 86.6 | |
(in bypass only at 110% overload per phase) |
|
|
|
| |
|
|
|
|
| |
Neutral output current (with 100% switch mode load) | 45.5 | 68.2 | 90.9 | 136.4 | |
(A) |
|
|
|
| |
|
|
|
|
| |
Output current protection (external to UPS, not | 40 | 60 | 80 | 120 | |
supplied) (A) |
|
|
|
| |
|
|
|
|
| |
Output frequency range (Hz) | 50/60 | 50/60 | 50/60 | 50/60 | |
|
|
|
|
| |
DC overcurrent protection and disconnect switch for | 26.4 | 39.6 | 52.7 | 78.9 | |
external safety: |
|
|
|
| |
DC voltage rating of the battery supply | +/- 192 | +/- 192 | +/- 192 | +/- 192 | |
Maximum available | 10 kA | 10 kA | 10 kA | 10 kA | |
|
|
|
|
|
23 |