Operating Environment
Operating conditions
Install the UPS in an indoor,
Note
Temperature
Range:
32° to 104°F /
0° to 40°C
Keep Ventilated
Relative
Humidity: <95%
No Conductive
Dust or
Corrosive
Fumes
Altitude derating table:
3,000 ft/914 m: 100% load
4,500 ft/1371 m: 95% load
6,000 ft/1828 m: 91% load
8,000 ft/2438 m: 86% load
10,000 ft/3048 m: 82% load
Heat dissipation
| BTU/hr at fully |
| BTU/hr at fully |
UPS size | charged batteries | UPS size | charged batteries |
|
|
|
|
10 kVA | 1,774 | 20 kVA | 3,624 |
|
|
|
|
15 kVA | 2,866 | 30 kVA | 5,486 |
|
|
|
|
Audible noise
UPS Sizes | Audible noise at 100% load | Audible noise at <70% load |
(1.09 yard/1 m from the UPS) | (1.09 yard/1 m from the UPS) | |
|
|
|
54 dBA | 45.4 dBA | |
|
|
|
58 dBA | 48.5 dBA | |
|
|
|
12 |