2. Expanded Functions
2.2.3 Timer
The T3H has 1000 points of timer.
Function type | Type | Address range | Quantity | Expression |
| code |
|
| example |
Timer register | T | 000 - 999 | 1000 words | T670 |
Timer device | T. | 000 - 999 | 1000 points | T.670 |
The proportion of the 0.01 s base and the 0.1 s base timers within this 1000 points can be specified by user. This setting information is stored in the system information.
10 ms Timer Range Setting: |
| |
T000 - T [ | ] | User setting (max. 999) |
NOTE |
|
|
|
|
|
T3H internally, the register ranges T000 to T511 and T512 to T999 are | |||||
handled separately. Therefore, index modification or table designation | |||||
across these ranges are not allowed. |
| ||||
For example) |
|
|
| ||
├─[ T450 TMOV | (100) D1000 ]- | Not allowed | |||
├─[ T450 |
|
|
|
|
|
TMOV | (62) | D1000 ]- | Allowed | ||
│ | TMOV | (38) | D1062 ]- |
| |
├─[ T512 |
|
2.2.4 Link register
The T3H has 2048 words of link register. This link register is prepared for the
Function type | Type | Address range | Quantity | Expression |
| code |
|
| example |
Link register | W | 0000 - 2047 | 2048 words | W1500 |
Link device | Z | 0000 - 999F | 16000 points | Z847E |
The link device Z corresponds to a bit in a link register W. The bit access as Z device is available for the leading 1000 words of W register.
User’s Manual 31