Manual mode

In this mode, the manipulation value MV can be directly controlled by the input value of MMV. MV differential limit for manual mode DMMV is effective. MH/ML and DMV are not effective.

When mode is changed from manual to auto or cascade, the operation is started from the current MV.

Cascade mode

This is a mode for PID cascade connection. PID is executed with CSV as set value.

Different from the auto mode, set value differential limit is not effective. Manipulation value upper/lower limit MH/ML and differential limit DMV are effective.

Bump-less changing from cascade mode to manual mode is available. (Manual mode manipulation

value MMV is over-written by current MV automatically. MMV MV)

And, bump-less changing from cascade mode to auto mode is available. (Auto mode set value ASV is over-written by current CSV automatically. ASV CSV)

MV tracking

This function is available in auto and cascade modes. When the tracking designation (A+10 bit 2) is ON, tracking input TMV is directly output as MV.

Manipulation value upper/lower limit MH/ML is effective, but differential limit DMV is not effective. When the tracking designation is changed to OFF, the operation is started from the current MV.

Note

FPID3 instruction is only usable on the main-program.

FPID3 instruction must be used under the constant scan mode. The constant scan interval can be selected in the range of 10 to 200 ms, 10 ms increments.

The data handled by the FPID3 instruction are % units. Therefore, process input value PVC, manipulation value MV, etc., should be converted to % units (scaling), before and/or after the FPID3 instruction.

User’s Manual 55

Image 57
Contents USER’S Manual Important Information Hazard Classifications General InformationWiring Safety Precautions InstallationOperation Maintenance Safety Label Terminology About This ManualT3 manuals VacContents Prosec T3H Section T3H Overview Introducing the T3H Differences between T3H and T3 Two types of T3H CPU modules are available T3H components CPU moduleRAM/ROM switch Mode control switchStatus LEDs Programmer port Battery coverComputer link port IC memory card slotExpansion interface module T3H CPU CH1 CH2CPU Power supply module RackExpansion cable Following types of I/O modules are available O moduleModule internal current consumption Data transmission moduleTOSLINE-S20LP AsciiSpecifications Functional specifications SFCRAS Instruction execution speed Tenr TeorTest DtstRST SETTset TrstSIN PID2COS TANInstruction execution speed cont’d Shown below Section Expanded Functions System operation Auto-RUN / Standby selection Timer interrupt intervalSaving the sampling trace condition Expanded registers External I/O registerAuxiliary register Link register TimerLink Global Special register File registerSEND/RECV Expanded FunctionsTOSLINE-S20 Expanded Functions Starting register Expanded file register data read MRADR S T Expanded file register data Write MWExpanded Functions TOSLINE-S20LP loop support Ethernet support Instructions Double-word multiplication and division D∗ Expanded Functions DSV Essential PID PID3Algorithm Control block diagramParameter details ASV ← ISV OperationExpanded Functions Floating point essential PID FPID3 Digital filter PVn = 1− FT⋅ PVC+ FT⋅ PVn − Here ≤ FT ASV differential limit DSV 0 to 100 %/∆ t Data range +1 ⋅C Expanded Functions Expanded data transfer Xfer Type Transfer parameter tableCPU register ↔ Expanded F register IC memory card CPU register ↔ S20/S20LP scan memory CPU register ↔ Eeprom D register When the data writing address range exceeds page boundary MID Network data send SendExpanded Functions S20LP T3H self-station RW100 RW101 RW227 Network data receive Recv Expanded Functions H0A Expanded Functions Prosec T3H Toshiba Corporation