2. Expanded Functions
T3H (self-station)
RW100
RW101
RW227
TOSLINE-S20LP
Station No. 3
T3H
D1000
D1001
D1127
When R0020 is ON, 128 words data starting with RW100 is transferred to D1000 and after of the T3H on which station No. 3 S20LP is installed.
When the operation is completed, the status is set in RW050 and instruction output comes ON.
Note
•Keep the input ON until the output comes ON.
•This instruction becomes error complete in the following cases. (ERF = S0051 is set to ON)
(1)Target station No. is invalid. (for S20LP)
(2) Invalid register designation. (In case of T and C registers, T → T and C → C is only possible)
(3)Source/destination register address range is out of valid range.
(4)Destination register is
(5)Response
(6)If expanded F register is designated;
-when MMR setting is not made.
-when IC card is not installed.
-when IC card is used to store program.
-when IC card is
•By using SW067, register
SW067
F | 9 | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
| SW | C | T |
| F | D | RW | LW | W | YW |
0: Write enable | Both F register in CPU and | |
1: Write protect | ||
expanded F register in IC card | ||
|
•Resetting the status register (operand B) is necessary at the first scan.
•When using the
User’s Manual 65