Toshiba TOSVERT VF-FS1 Series instruction manual Network variable list the other

Page 19

E6581373

6.3. Network variable list (the other)

The other network variables are shown in the table below.

.

LIU

LIU

Variables

SNVT_type.

unit

Default value

007Z

006Z

 

 

0.5%,1

 

v

 

nviResetFault

SNVT_switch

{0.0%, 0}

v

 

nviInvSetFreq

SNVT_freq_hz

0.1Hz

3276.7Hz = invalid

v

 

nvoStatusWord

SNVT_state

boolean

 

v

 

nvoDrvFeedback

SNVT_switch

0.5%,1

 

v

 

nvoInvOutFreq

SNVT_freq_hz

0.1Hz

 

v

 

nvoDrvAlarm

SNVT_switch

0.5%,1

 

v

 

nvoAlarmWord

SNVT_state

boolean

 

---

 

nvoDrvThermal

SNVT_lev_percent

0.005%

 

---

 

nvoMotorThermal

SNVT_lev_percent

0.005%

 

v

 

nvoTorque

SNVT_lev_percent

0.005%

 

v

 

nvoDrvEnergy

SNVT_elec_kwh_l

0.1kWh

 

v

 

nvoDigitalIn1

SNVT_switch

0.5%,1

 

v

 

nvoDigitalIn2

SNVT_switch

0.5%,1

 

---

 

nvoDigitalIn3

SNVT_switch

0.5%,1

 

---

 

nvoDigitalIn4

SNVT_switch

0.5%,1

 

---

 

nvoDigitalIn5

SNVT_switch

0.5%,1

 

---

 

nvoDigitalIn6

SNVT_switch

0.5%,1

 

---

 

nvoDigitalIn7

SNVT_switch

0.5%,1

 

---

 

nvoDigitalIn8

SNVT_switch

0.5%,1

 

---

 

nvoDigitalInput

SNVT_state

boolean

 

---

 

nvoAnalogIn1

SNVT_lev_percent

0.005%

 

v

 

nvoAnalogIn2

SNVT_lev_percent

0.005%

 

---

 

nvoAnalogIn3

SNVT_lev_percent

0.005%

 

v

 

nviRelay1

SNVT_switch

0.5%,1

{0.0%, 0}

---

 

nviDigitalOut1

SNVT_switch

0.5%,1

{0.0%, 0}

---

 

nviDigitalOut2

SNVT_switch

0.5%,1

{0.0%, 0}

---

 

nviDigitalOutput

SNVT_state

boolean

{0,0,...,0}

---

 

nviAnalogOut1

SNVT_lev_percent

0.005%

0.000%

---

 

nviAnalogOut2

SNVT_lev_percent

0.005%

0.000%

v

 

nviEmergOverride

SNVT_hvac_emerg

binary

 

v

 

nvoEmergStatus

SNVT_hvac_emerg

binary

 

v

 

nviParamCmd

SNVT_preset

binary

 

v

 

nvoParamResp

SNVT_preset

binary

 

v

 

nvoTypeVer

SNVT_str_asc

Ascii

 

v

 

nciPwUpOutTm

SNVT_time_sec

0.1s

0.0s

v: Support, ---:Not support, *LIU006Z is under development.

- 18 -

Image 19
Contents E6581373 Handling in general IntroductionTable of Contents E6581373 Applicable model System configurationScope OverviewLIU007Z for VF-FS1 Names and functions of main partsOutline view LIU006ZService LED DiagnosticsLED OFF Fault LEDStatus LED LED on LED OFFRS485 communication port Neuron ID ConfigurationsService pin Device interface XIF file Inverter configurationsLIU007Z Command & Setpoint selection Local/RemoteReference parameter of the inverter Functional profile supported by this option Functional profileObject id Object map Node Object functional blockNetwork variables Node Object NviRequest Object Request NciLocation Location Label NvoStatus Object Status Object map is the following ACMotorDrive functional blockLIU Network variable list VSD601011Network variable list the other NciMaxSpeed Maximum Speed Configuration propertiesNciMinSpeed Minimum Speed NciSndHrtBt Send Heartbeat Time NciRcvHrtBt Receive Heartbeat TimeNciMinOutTm Minimum Send Time NciNmlFreq Nominal Motor Frequency NciNmlSpeed Nominal Motor Speed in min-1NciRampUpTm Ramp Up Time NciPwUpOutTm Power up delay time NciDrvSpeedScale Default value for nviDrvSpeedScaleNciRampDownTm Ramp Down Time NviDrvSpeedScale Drive Speed Setpoint Scaling NviResetFault Fault Reset CommandInput network variables NviDrvSpeedStpt Drive Speed SetpointLIU007Z LIU006Z NviInvSetFreq Frequency SetpointNviRelay1 /nviDigitalOut1,2 Control of Digital Output NviDigitalOutput Control of All Digital OutputsNviEmergOverride Emergency stop NviAnalogOut1,2 Control of Analog outputLnlearnvalue NviParamCmd Parameter accessLnrecall LnlearncurrentOutput network variables NvoDrvFeedback Velocity Feedback NvoDrvAlarm AlarmNvoStatusWord Inverter Status NvoTorque Motor Torque Monitor NvoAlarmWord Alarm StatusNvoDrvThermal Drive Thermal State NvoMotorThermal Motor Thermal StateNvoDigitalInput All Digital Inputs Monitor NvoDrvEnergy Cumulative Input EnergyNvoDigitalIn1 to 8 Digital Input Monitor NvoEmergStatus Emergency Status NvoAnalogIn1 to 3 Analog Input MonitorToshiba NvoParamResp Parameter Access ResponseNvoTypeVer Identification AsciiBinding ProcedureOption unit reset method Example usageCommunication health management Parameter access method E6581373 ANSI/EIA/CEA Specifications