Toshiba TOSVERT VF-FS1 Series NvoDrvFeedback Velocity Feedback, NvoStatusWord Inverter Status

Page 29

E6581373

6.6.6. nvoDrvFeedback (Velocity Feedback)

Output network variable SNVT type: SNVT_switch (95)

It provides stopped / running status and low resolution output speed of the motor. - Specification

nvoDrvFeedback

Operation

value

state

 

N/A

0

Stop

0.0 to 127.5%

1

Drive at 0.0 to 127.5% speed.

value = (Drive frequency) / nciNmlFreq / nviDrvSpeedScale

 

 

N.B.: When the speed exceeds the 127.5%, “value” is limited to 127.5%

If “nviDrvSpeedScale” was set to 0, nvoDrvFeedback.value shows 0.0%.

The value exceeded to the resolution will be rounded.

6.6.7. nvoStatusWord (Inverter Status)

Output network variable SNVT type: SNVT_state (83) It provides the inverter status.

- Format:

Bit

Description

0

1

0

Fault

No fault

Fault

1

Warning

No warning

Warning

2

Running

Stopped

Running

3

Rotation

Forward

Reverse

4

Ready

Disable

Enable

5

Command from the network

Not from the network

From the network

6

Setpoint from the network

Not from the network

From the network

7

At setpoint

Setpoint not reached

Setpoint reached

8-15

(reserved)

----------------

----------------

N.B.: On LIU007Z, “At setpoint” bit could work under the condition that VF-FS1 software version was V106 or successor,

6.6.8. nvoDrvAlarm (Alarm)

Output network variable SNVT type: SNVT_switch (95) It provides the inverter fault.

- Status

nvoDrvAlarm

 

Status

value

 

state

 

 

0%

 

0

No fault

100%

 

1

Fault

*Refer to “nvoAlarmWord” for detail fault information.

- 28 -

Image 29
Contents E6581373 Handling in general IntroductionTable of Contents E6581373 Scope System configurationOverview Applicable modelOutline view Names and functions of main partsLIU006Z LIU007Z for VF-FS1LED DiagnosticsService LED Status LED Fault LEDLED on LED OFF OFFRS485 communication port Service pin Device interface XIF file ConfigurationsInverter configurations Neuron IDLIU007Z Command & Setpoint selection Local/RemoteReference parameter of the inverter Object id Functional profileFunctional profile supported by this option Network variables Node Object Node Object functional blockObject map NviRequest Object Request NciLocation Location LabelNvoStatus Object Status Object map is the following ACMotorDrive functional blockLIU Network variable list VSD601011Network variable list the other NciMinSpeed Minimum Speed Configuration propertiesNciMaxSpeed Maximum Speed NciMinOutTm Minimum Send Time NciRcvHrtBt Receive Heartbeat TimeNciSndHrtBt Send Heartbeat Time NciRampUpTm Ramp Up Time NciNmlSpeed Nominal Motor Speed in min-1NciNmlFreq Nominal Motor Frequency NciRampDownTm Ramp Down Time NciDrvSpeedScale Default value for nviDrvSpeedScaleNciPwUpOutTm Power up delay time Input network variables NviResetFault Fault Reset CommandNviDrvSpeedStpt Drive Speed Setpoint NviDrvSpeedScale Drive Speed Setpoint ScalingNviRelay1 /nviDigitalOut1,2 Control of Digital Output NviInvSetFreq Frequency SetpointNviDigitalOutput Control of All Digital Outputs LIU007Z LIU006ZNviEmergOverride Emergency stop NviAnalogOut1,2 Control of Analog outputLnrecall NviParamCmd Parameter accessLnlearncurrent LnlearnvalueOutput network variables NvoStatusWord Inverter Status NvoDrvAlarm AlarmNvoDrvFeedback Velocity Feedback NvoDrvThermal Drive Thermal State NvoAlarmWord Alarm StatusNvoMotorThermal Motor Thermal State NvoTorque Motor Torque MonitorNvoDigitalIn1 to 8 Digital Input Monitor NvoDrvEnergy Cumulative Input EnergyNvoDigitalInput All Digital Inputs Monitor NvoEmergStatus Emergency Status NvoAnalogIn1 to 3 Analog Input MonitorNvoTypeVer Identification NvoParamResp Parameter Access ResponseAscii ToshibaOption unit reset method ProcedureExample usage BindingCommunication health management Parameter access method E6581373 ANSI/EIA/CEA Specifications