6.6.6. nvoDrvFeedback (Velocity Feedback)
Output network variable SNVT type: SNVT_switch (95)
It provides stopped / running status and low resolution output speed of the motor. - Specification
nvoDrvFeedback | Operation | ||
value | state | ||
| |||
N/A | 0 | Stop | |
0.0 to 127.5% | 1 | Drive at 0.0 to 127.5% speed. | |
value = (Drive frequency) / nciNmlFreq / nviDrvSpeedScale | |||
|
|
N.B.: When the speed exceeds the 127.5%, “value” is limited to 127.5%
If “nviDrvSpeedScale” was set to 0, nvoDrvFeedback.value shows 0.0%.
The value exceeded to the resolution will be rounded.
6.6.7. nvoStatusWord (Inverter Status)
Output network variable SNVT type: SNVT_state (83) It provides the inverter status.
- Format:
Bit | Description | 0 | 1 |
0 | Fault | No fault | Fault |
1 | Warning | No warning | Warning |
2 | Running | Stopped | Running |
3 | Rotation | Forward | Reverse |
4 | Ready | Disable | Enable |
5 | Command from the network | Not from the network | From the network |
6 | Setpoint from the network | Not from the network | From the network |
7 | At setpoint | Setpoint not reached | Setpoint reached |
(reserved) |
N.B.: On LIU007Z, “At setpoint” bit could work under the condition that
6.6.8. nvoDrvAlarm (Alarm)
Output network variable SNVT type: SNVT_switch (95) It provides the inverter fault.
- Status
nvoDrvAlarm |
| Status | |
value |
| state | |
|
| ||
0% |
| 0 | No fault |
100% |
| 1 | Fault |
*Refer to “nvoAlarmWord” for detail fault information.