E6581373
- Valid range
Bit |
| LIU007Z |
|
| LIU006Z | ||
Terminal |
| Parameter | Terminal | Parameter | |||
|
| ||||||
0 |
|
|
|
|
| ||
1 |
|
|
|
|
| ||
2 |
|
|
|
|
| ||
|
| Under | Development |
| |||
3 |
|
|
| ||||
4 |
|
|
|
|
| ||
|
|
|
|
| |||
5 |
|
|
|
|
| ||
|
|
|
|
|
If multiple digital output control signals are used at the same time, the output value is the OR of all digital output controls.
6.5.7. nviAnalogOut1,2 (Control of Analog output)
Input network variable (Reserved) SNVT type: SNVT_lev_percent (81) They enable the analog output control.
- Valid range: 0.000 to 100.000%
(Output value is not adjusted by the inverter parameter “fm”, ”am”) - Unit: 0.005% (The resolution depends on the inverter specification)
When the variables will be used, the inverter parameters must be assigned.
Name | LIU007Z |
| LIU006Z | ||||
Terminal | Parameter |
| Terminal |
| Parameter |
| |
|
|
|
| ||||
nviAnalogOut1 |
| Under | Development |
| |||
nviAnalogOut2 |
|
|
|
|
| ||
|
|
|
|
|
6.5.8. nviEmergOverride (Emergency stop)
Input network variable
SNVT type: SNVT_have_emerg (103)
It provides an emergency stop of the motor. Emergency stop can be configured by Emergency stop selection (f603) to coast stop, slow down stop or emergency DC braking (refer to the inverter instruction manual for details).
- Valid range
Value | Command | Description | |
0 | Remove emergency | EMERG_NORMAL (No Emergency mode) | |
1 |
| EMERG_PRESSURIZE (Emergency pressurize mode) | |
2 |
| EMERG_DEPRESSURIZE (Emergency depressurize mode) | |
3 | Emergency stop | EMERG_PURGE (Emergency purge mode) | |
4 | EMERG_SHUTDOWN (Emergency shutdown mode) | ||
| |||
5 |
| EMERG_FIRE (Emergency fire mode) | |
6 to 255 |
|
N.B.: “Remove emergency” command clears a fault and resets the inverter.
- 25 -