E6581373
3.7. Reference parameter of the inverter
Reference parameter of the inverter is listed below.
Title |
| Name | Description | |
acc |
| Acceleration time |
| |
dec |
| Deceleration time |
| |
fh |
| Maximum frequency | Do not change these parameters, because | |
ul |
| Upper limit frequency | the LONWORKS option unit using them. | |
ll |
| Lower limit frequency |
| |
vl |
| Base frequency 1 |
| |
|
|
| Network command has priority when the | |
cmod |
| Command mode selection | inverter is Remote mode. (See previous | |
|
|
| section) | |
|
|
| Network setpoint has priority when the | |
fmod |
| Setpoint mode selection | inverter is Remote mode. (See previous | |
|
|
| section) | |
f111 | ... | Logic input terminal function | Set proper value if use (See the inverter | |
instruction manual). | ||||
|
|
| ||
f603 |
| Emergency stop selection | For “nviEmergOverride” | |
f800 |
| Communication baud rate | Set “1” (default) | |
f801 |
| Communication parity | Set “1” (default) | |
f803 |
| Communication error trip time | Set properly value | |
f829 |
| Communication protocol | Set “1” (MODBUS) | |
|
|
|
| |
f851 |
| Operation at network disconnection | See “section 7.4 Communication health | |
| management”. | |||
|
|
|
Warning
Mandatory
For LIU007Z, set up “Communication error trip function (f803, see the inverter instruction manual for details)” to stop the inverter when this option unit is deactivated by an unusual event such as tripping, an operating error, power outage, failure, etc. Deactivated option unit may cause an accident, if the “Communication error trip function” is not properly set up.
- 11 -