Toshiba TOSVERT VF-FS1 Series instruction manual Specifications, Ansi/Eia/Cea

Page 38

E6581373

8. Specifications

Item

Specification

 

Notes

Number of domains

2

 

 

Number of address

37

 

 

entries

 

 

 

 

 

Number of alias tables

8

 

 

Communication

Free topology transceiver

ANSI/EIA/CEA 709.3

transceiver

TP/FT-10 channel type.

 

 

Baudrate

78kbps

 

 

Protocol

LonTalk

ANSI/EIA 709.1

Communication signal

2 wires plus shield

NETA, Sheild, NETB

 

Free topology:

 

 

 

Between devices: 400m or less

When recommended cable is used:

Transmission distance

Total cable length: 500m or less

Bus topology ( both terminated):

Level 4/22AWG

 

 

Total cable length: 1400m or less

 

 

 

Stub length: 3m or less

 

 

Functional block

Node Object (0)

LONMARK functional profile

Variable Speed Motor Drive (1)

Variable Speed Motor Drive

 

Number of

Input network variables: 8

 

 

Output network variables: 17

 

 

Network variables

 

 

Configuration properties: 12

 

 

 

 

 

Number of connected

64 nodes at maximum

However, a

host and routers are

nodes

counted as one node.

 

Service pin function

Mechanical switch (SW2)

Used for notification of Neuron ID to

the host.

 

 

 

 

 

 

Applicable terminal block

Terminal block

Detachable terminal block 3-pole

Manufacturer: PHOENIX CONTACT

 

 

Type-Form

: MSTB 2,5/3-ST-5,08

- 37E -

Image 38
Contents E6581373 Introduction Handling in generalTable of Contents E6581373 Overview System configurationScope Applicable modelLIU006Z Names and functions of main partsOutline view LIU007Z for VF-FS1LED DiagnosticsService LED LED on LED OFF Fault LEDStatus LED OFFRS485 communication port Inverter configurations ConfigurationsService pin Device interface XIF file Neuron IDCommand & Setpoint selection Local/Remote LIU007ZReference parameter of the inverter Object id Functional profileFunctional profile supported by this option Network variables Node Object Node Object functional blockObject map NciLocation Location Label NviRequest Object RequestNvoStatus Object Status ACMotorDrive functional block Object map is the followingNetwork variable list VSD601011 LIUNetwork variable list the other NciMinSpeed Minimum Speed Configuration propertiesNciMaxSpeed Maximum Speed NciMinOutTm Minimum Send Time NciRcvHrtBt Receive Heartbeat TimeNciSndHrtBt Send Heartbeat Time NciRampUpTm Ramp Up Time NciNmlSpeed Nominal Motor Speed in min-1NciNmlFreq Nominal Motor Frequency NciRampDownTm Ramp Down Time NciDrvSpeedScale Default value for nviDrvSpeedScaleNciPwUpOutTm Power up delay time NviDrvSpeedStpt Drive Speed Setpoint NviResetFault Fault Reset CommandInput network variables NviDrvSpeedScale Drive Speed Setpoint ScalingNviDigitalOutput Control of All Digital Outputs NviInvSetFreq Frequency SetpointNviRelay1 /nviDigitalOut1,2 Control of Digital Output LIU007Z LIU006ZNviAnalogOut1,2 Control of Analog output NviEmergOverride Emergency stopLnlearncurrent NviParamCmd Parameter accessLnrecall LnlearnvalueOutput network variables NvoStatusWord Inverter Status NvoDrvAlarm AlarmNvoDrvFeedback Velocity Feedback NvoMotorThermal Motor Thermal State NvoAlarmWord Alarm StatusNvoDrvThermal Drive Thermal State NvoTorque Motor Torque MonitorNvoDigitalIn1 to 8 Digital Input Monitor NvoDrvEnergy Cumulative Input EnergyNvoDigitalInput All Digital Inputs Monitor NvoAnalogIn1 to 3 Analog Input Monitor NvoEmergStatus Emergency StatusAscii NvoParamResp Parameter Access ResponseNvoTypeVer Identification ToshibaExample usage ProcedureOption unit reset method Binding Communication health management Parameter access method E6581373 Specifications ANSI/EIA/CEA