Toshiba TOSVERT VF-FS1 Series instruction manual NvoAnalogIn1 to 3 Analog Input Monitor

Page 32

E6581373

The relationship between the network variables and input terminals is shown in below.

Variables

LIU007Z

LIU006Z

nvoDigitalIn1

F terminal

 

 

nvoDigitalIn2

R terminal

 

 

nvoDigitalIn3

-------

 

 

 

Under Development

 

nvoDigitalIn4

-------

 

nvoDigitalIn5

 

 

 

-------

 

 

nvoDigitalIn6

-------

 

 

nvoDigitalIn7

-------

 

 

nvoDigitalIn8

-------

 

 

6.6.16. nvoAnalogIn1 to 3 (Analog Input Monitor)

Output network variable

SNVT type: SNVT_lev_percent (81)

They provide the inverter analog input terminal state in percentage.

-Valid range: 0.000 to 100.000%

-Unit: 0.005% (The resolution depends on the inverter specification)

The adjustment of analog input value is possible to set the inverter parameter (f470 to f475) (Refer to the inverter instruction manual for details).

The relationship between the network variable and the terminal is shown in the table below.

Name

LIU007Z

 

LIU006Z

nvoAnalogIn1

-----

 

 

 

 

Under development

 

nvoAnalogIn2

VIB terminal

 

 

nvoAnalogIn3

-----

 

 

 

 

 

 

When RR/S4 terminal has Logic input terminal function, “nvoAnalogIn1” always shows 0.000%.

6.6.17. nvoEmergStatus (Emergency Status)

Output network variable

SNVT type: SNVT_have_emerg (103)

It provides the response against an emergency stop of the inverter (nviEmergOverride). When the node received “nviEmergOverride” network variable, it propagates the information to the network.

- Valid range

Value

Status

Description

0

Trip release

EMERG_NORMAL (No Emergency mode)

1

 

EMERG_PRESSURIZE (Emergency pressurize mode)

2

 

EMERG_DEPRESSURIZE (Emergency depressurize mode)

3

Emergency stop

EMERG_PURGE (Emergency purge mode)

4

EMERG_SHUTDOWN (Emergency shutdown mode)

 

5

 

EMERG_FIRE (Emergency fire mode)

6 to 255

 

---

- 31 -

Image 32
Contents E6581373 Introduction Handling in generalTable of Contents E6581373 System configuration ScopeOverview Applicable modelNames and functions of main parts Outline viewLIU006Z LIU007Z for VF-FS1LED DiagnosticsService LED Fault LED Status LEDLED on LED OFF OFFRS485 communication port Configurations Service pin Device interface XIF fileInverter configurations Neuron IDCommand & Setpoint selection Local/Remote LIU007ZReference parameter of the inverter Object id Functional profileFunctional profile supported by this option Network variables Node Object Node Object functional blockObject map NciLocation Location Label NviRequest Object RequestNvoStatus Object Status ACMotorDrive functional block Object map is the followingNetwork variable list VSD601011 LIUNetwork variable list the other NciMinSpeed Minimum Speed Configuration propertiesNciMaxSpeed Maximum Speed NciMinOutTm Minimum Send Time NciRcvHrtBt Receive Heartbeat TimeNciSndHrtBt Send Heartbeat Time NciRampUpTm Ramp Up Time NciNmlSpeed Nominal Motor Speed in min-1NciNmlFreq Nominal Motor Frequency NciRampDownTm Ramp Down Time NciDrvSpeedScale Default value for nviDrvSpeedScaleNciPwUpOutTm Power up delay time NviResetFault Fault Reset Command Input network variablesNviDrvSpeedStpt Drive Speed Setpoint NviDrvSpeedScale Drive Speed Setpoint ScalingNviInvSetFreq Frequency Setpoint NviRelay1 /nviDigitalOut1,2 Control of Digital OutputNviDigitalOutput Control of All Digital Outputs LIU007Z LIU006ZNviAnalogOut1,2 Control of Analog output NviEmergOverride Emergency stopNviParamCmd Parameter access LnrecallLnlearncurrent LnlearnvalueOutput network variables NvoStatusWord Inverter Status NvoDrvAlarm Alarm NvoDrvFeedback Velocity Feedback NvoAlarmWord Alarm Status NvoDrvThermal Drive Thermal StateNvoMotorThermal Motor Thermal State NvoTorque Motor Torque MonitorNvoDigitalIn1 to 8 Digital Input Monitor NvoDrvEnergy Cumulative Input EnergyNvoDigitalInput All Digital Inputs Monitor NvoAnalogIn1 to 3 Analog Input Monitor NvoEmergStatus Emergency StatusNvoParamResp Parameter Access Response NvoTypeVer IdentificationAscii ToshibaProcedure Option unit reset methodExample usage BindingCommunication health management Parameter access method E6581373 Specifications ANSI/EIA/CEA