Introduction

Thank you for purchasing the “LONWORKS option unit” for TOSVERT VF-FS1 series inverter.

Before using LONWORKS option unit, carefully read this function manual in order to completely and correctly utilize its excellent performance.

After reading this function manual, please keep it handy for future reference.

For details of its general handling, see an instruction manual attached with the option unit.

*Echelon®, LONWORKS®, LONMARK®, LonTalk®, Neuron®, are the registered trademarks or the trademarks of Echelon Corporation in the USA and other countries.

*LONMARK and the LONMARK Logo are managed, granted, and used by LONMARK International under a license granted by Echelon Corporation.

Handling in general

Danger

 

 

 

Do not connect or disconnect a network cable while the inverter power is on.

 

Prohibited

It may lead to electric shocks or fire.

 

 

 

 

 

See the instruction manual attached with the option unit for cautions the handling.

 

Mandatory

Otherwise, it may lead to electric shocks, fire, injuries or damage to product.

 

 

 

 

Network control

 

 

 

 

 

 

 

Danger

 

 

 

Do not send the value out of the valid range to network variables.

 

Prohibited

Otherwise, the motor may suddenly start/stop and that may result in injuries.

 

 

 

 

 

Use an additional safety device with your system to prevent a serious accident due to the

 

Mandatory

network malfunctions.

 

Usage without an additional safety device may cause an accident.

Warning

Mandatory

Set up “Communication error trip function (see below)” to stop the inverter when the option unit is deactivated by an unusual event such as tripping, an operating error, power outage, failure, etc.

- Receive heart beat timer

See the “nciRcvHrtBt (Receive Heartbeat Time)” for details.

Deactivated option unit may cause an accident, if the “Communication error trip function” is not properly set up.

Make sure that the operation signals are STOP before clearing the inverter fault. The motor may suddenly start and that may result in injuries.

Notes on operation

Notes

When the control power is shut off by the instantaneous power failure, communication will be unavailable for a while.

The Life of EEPROM is approximately 10000 times. Avoid writing data more than 10000 times to the same parameter of the inverter and configuration properties on LONWORKS option unit.

- 1 -

Image 2
Contents E6581373 Introduction Handling in generalTable of Contents E6581373 Overview System configurationScope Applicable modelLIU006Z Names and functions of main partsOutline view LIU007Z for VF-FS1LED DiagnosticsService LED LED on LED OFF Fault LEDStatus LED OFFRS485 communication port Inverter configurations ConfigurationsService pin Device interface XIF file Neuron IDCommand & Setpoint selection Local/Remote LIU007ZReference parameter of the inverter Object id Functional profileFunctional profile supported by this option Network variables Node Object Node Object functional blockObject map NciLocation Location Label NviRequest Object RequestNvoStatus Object Status ACMotorDrive functional block Object map is the followingNetwork variable list VSD601011 LIUNetwork variable list the other NciMinSpeed Minimum Speed Configuration propertiesNciMaxSpeed Maximum Speed NciMinOutTm Minimum Send Time NciRcvHrtBt Receive Heartbeat TimeNciSndHrtBt Send Heartbeat Time NciRampUpTm Ramp Up Time NciNmlSpeed Nominal Motor Speed in min-1NciNmlFreq Nominal Motor Frequency NciRampDownTm Ramp Down Time NciDrvSpeedScale Default value for nviDrvSpeedScaleNciPwUpOutTm Power up delay time NviDrvSpeedStpt Drive Speed Setpoint NviResetFault Fault Reset CommandInput network variables NviDrvSpeedScale Drive Speed Setpoint ScalingNviDigitalOutput Control of All Digital Outputs NviInvSetFreq Frequency SetpointNviRelay1 /nviDigitalOut1,2 Control of Digital Output LIU007Z LIU006ZNviAnalogOut1,2 Control of Analog output NviEmergOverride Emergency stopLnlearncurrent NviParamCmd Parameter accessLnrecall LnlearnvalueOutput network variables NvoStatusWord Inverter Status NvoDrvAlarm AlarmNvoDrvFeedback Velocity Feedback NvoMotorThermal Motor Thermal State NvoAlarmWord Alarm StatusNvoDrvThermal Drive Thermal State NvoTorque Motor Torque MonitorNvoDigitalIn1 to 8 Digital Input Monitor NvoDrvEnergy Cumulative Input EnergyNvoDigitalInput All Digital Inputs Monitor NvoAnalogIn1 to 3 Analog Input Monitor NvoEmergStatus Emergency StatusAscii NvoParamResp Parameter Access ResponseNvoTypeVer Identification ToshibaExample usage ProcedureOption unit reset method BindingCommunication health management Parameter access method E6581373 Specifications ANSI/EIA/CEA