6.5. Input network variables
6.5.1. nviDrvSpeedStpt (Drive Speed Setpoint)
Input network variable, Variable Speed Drive 6010_11 (Mandatory) SNVT type: SNVT_switch (95)
It provides start/stop control and a low resolution speed setpoint as a percent of nominal speed. Output frequency = “nciNmlFreq” x “nviDrvSpeedStpt.value” x “nviDrvSpeedScale”
- Valid range
nviDrvSpeedStpt | Operation | ||
value | state | ||
| |||
N/A | 0 | Stop | |
0.0 to 100.0% | 1 | Drive at the speed from 0.5% to 100% | |
100.5 to 127.5% | 1 | Drive at 100% speed | |
N/A | AUTO (Invalid) |
- Unit (nviDrvSpeedStpt.value): 0.5%
- Default value: 0.0% (value), AUTO (state =
Default value will be adopted at
N.B. The value exceeded to the inverter setpoint resolution will be rounded.
6.5.2. nviDrvSpeedScale (Drive Speed Setpoint Scaling)
Input network variable, Variable Speed Drive 6010_11 (Optional) SNVT type: SNVT_lev_percent (81)
This input network variable provides scaling for “nviDrvSpeedStpt”. Negative values indicate a motor direction in reverse.
-Valid range:
-Unit: 0.005%
-Default value: “nciDrvSpeedScale”
Default value will be adopted at
N.B. The value exceeded to the inverter setpoint resolution will be rounded.
6.5.3. nviResetFault (Fault Reset Command)
Input network variable
SNVT type: SNVT_switch (95)
This command clears the inverter fault when the inverter is under a fault that can be cleared. - Valid range
nviResetFault |
| Command | |
value |
| state | |
|
| ||
N/A |
| 0, | Invalid |
0.0% |
| 1 | |
|
| ||
0.5% to 127.5% |
| 1 | Clear a fault and reset the inverter. |