Toshiba TOSVERT VF-FS1 Series instruction manual Communication health management, LIU007Z LIU006Z

Page 35

E6581373

7.4. Communication health management

This option unit has communication health management function.

1. Communication time out function (nciRcvHrtBt)

This value manages the communication time out function. This option unit would initialize the drive command/setpoint variables and try to stop the motor in case of not receiving an update of the following variables within the specified Receive Heartbeat time (nciRcvHrtBt).

-nviDrvSpeedStpt

-nviDrvSpeedScale

-nviInvOutFreq

In this case, the inverter output behavior can be determined by the parameter f851. However, next selections are invalid.

-None (continued operation)

2.Node health transmission function (nciSndHrtBt, nciMinOutTm)

This option unit informs the network manager to its own health. Network variables controlled by this function are shown in the table below.

Variables

LIU007Z

 

LIU006Z

nciSndHrtBt

nciMinOutTm

nciSndHrtBt

nciMinOutTm

 

nvoDrvSpeed

v

 

v

 

 

nvoDrvCurnt

v

 

v

 

 

nvoDrvVolt

v

 

v

 

 

nvoDrvPwr

v

 

v

 

 

nvoDrvRunHours

v

 

v

 

 

nvoStatusWord

v

 

v

 

 

nvoDrvFeedback

v

 

v

 

 

nvoInvOutFreq

v

 

v

 

 

nvoDrvAlarm

v

 

v

 

 

nvoAlarmWord

v

 

v

 

 

nvoDrvThermal

 

 

 

 

 

nvoMotorThermal

v

 

v

 

 

nvoTorque

 

 

 

nvoDrvEnergy

v

 

v

 

 

nvoDigitalIn1

v

 

v

Under Development

nvoDigitalIn2

v

 

v

 

 

 

nvoDigitalIn3

 

 

 

 

 

nvoDigitalIn4

 

 

 

 

 

nvoDigitalIn5

 

 

 

 

 

nvoDigitalIn6

 

 

 

 

 

nvoDigitalIn7

 

 

 

 

 

nvoDigitalIn8

 

 

 

 

 

nvoDigitalInput

 

 

 

 

 

nvoAnalogIn1

v

 

v

 

 

nvoAnalogIn2

 

 

 

nvoAnalogIn3

 

 

 

 

 

nvoEmergStatus

---

 

---

 

 

nvoParamResp

---

 

---

 

 

nvoTypeVer

---

 

---

 

 

v:controlled by nciSndHrtBt and nciMinOutTm

-34 -

Image 35
Contents E6581373 Handling in general IntroductionTable of Contents E6581373 Applicable model System configurationScope OverviewLIU007Z for VF-FS1 Names and functions of main partsOutline view LIU006ZLED DiagnosticsService LED OFF Fault LEDStatus LED LED on LED OFFRS485 communication port Neuron ID ConfigurationsService pin Device interface XIF file Inverter configurationsLIU007Z Command & Setpoint selection Local/RemoteReference parameter of the inverter Object id Functional profileFunctional profile supported by this option Network variables Node Object Node Object functional blockObject map NviRequest Object Request NciLocation Location LabelNvoStatus Object Status Object map is the following ACMotorDrive functional blockLIU Network variable list VSD601011Network variable list the other NciMinSpeed Minimum Speed Configuration propertiesNciMaxSpeed Maximum Speed NciMinOutTm Minimum Send Time NciRcvHrtBt Receive Heartbeat TimeNciSndHrtBt Send Heartbeat Time NciRampUpTm Ramp Up Time NciNmlSpeed Nominal Motor Speed in min-1NciNmlFreq Nominal Motor Frequency NciRampDownTm Ramp Down Time NciDrvSpeedScale Default value for nviDrvSpeedScaleNciPwUpOutTm Power up delay time NviDrvSpeedScale Drive Speed Setpoint Scaling NviResetFault Fault Reset CommandInput network variables NviDrvSpeedStpt Drive Speed SetpointLIU007Z LIU006Z NviInvSetFreq Frequency SetpointNviRelay1 /nviDigitalOut1,2 Control of Digital Output NviDigitalOutput Control of All Digital OutputsNviEmergOverride Emergency stop NviAnalogOut1,2 Control of Analog outputLnlearnvalue NviParamCmd Parameter accessLnrecall LnlearncurrentOutput network variables NvoStatusWord Inverter Status NvoDrvAlarm AlarmNvoDrvFeedback Velocity Feedback NvoTorque Motor Torque Monitor NvoAlarmWord Alarm StatusNvoDrvThermal Drive Thermal State NvoMotorThermal Motor Thermal StateNvoDigitalIn1 to 8 Digital Input Monitor NvoDrvEnergy Cumulative Input EnergyNvoDigitalInput All Digital Inputs Monitor NvoEmergStatus Emergency Status NvoAnalogIn1 to 3 Analog Input MonitorToshiba NvoParamResp Parameter Access ResponseNvoTypeVer Identification AsciiBinding ProcedureOption unit reset method Example usageCommunication health management Parameter access method E6581373 ANSI/EIA/CEA Specifications