Toshiba TOSVERT VF-FS1 Series instruction manual Output network variables

Page 28

E6581373

6.6. Output network variables

6.6.1. Output network variable update

Normally, output network variables are updated when the inverter status was changed. Automatic transmission function is also prepared by “nciSndHrtBt (Send Heartbeat Time)”, “nciMinOutTm (Minimum Send Time)” configuration properties.

See section 7.4 “Communication health management” for detail.

6.6.2. nvoDrvCurnt (Drive Output Current)

Output network variable, Variable Speed Drive 6010_11 (Optional)

SNVT type: SNVT_amp (1)

It provides the inverter output current in amperes.

-Valid range: 0.0 to 3276.6 A It is overwritten 0.0A when the inverter faulted.)

-Unit: 0.1 A

6.6.3.nvoDrvSpeed (Drive Speed Feedback)

Output network variable, Variable Speed Drive 6010_11 (Mandatory) SNVT type: SNVT_lev_percent (81)

It provides the motor speed as a percentage of the nominal speed. Negative value means a speed in reverse.

-Valid range: -163.840 to 163.830%

-Unit: 0.005% (The resolution depends on the inverter specification)

N.B.: It indicates the rotating direction at the time of a stop, only when at the time of the operation starts after changing rotating direction. However, the rotating direction of the inverter performs correctly.

6.6.4. nvoDrvRunHours (Drive Total Running Hours)

Output network variable, Variable Speed Drive 6010_11 (Optional) SNVT_type: SNVT_time_hour (124)

This output network variable provides the total operation time for the motor in running hours.

-Valid range: 0 to 65534 h (The overflow caused the value to return 0.)

-Unit: 1 h

6.6.5.nvoInvOutFreq (Frequency Feedback)

Output network variable

SNVT type: SNVT_freq_hz (76)

It provides the inverter output frequency.

-Valid range: 0.0Hz to 3276.6Hz

-Unit: 0.1Hz

- 27 -

Image 28
Contents E6581373 Introduction Handling in generalTable of Contents E6581373 System configuration ScopeOverview Applicable modelNames and functions of main parts Outline viewLIU006Z LIU007Z for VF-FS1Service LED DiagnosticsLED Fault LED Status LEDLED on LED OFF OFFRS485 communication port Configurations Service pin Device interface XIF fileInverter configurations Neuron IDCommand & Setpoint selection Local/Remote LIU007ZReference parameter of the inverter Functional profile supported by this option Functional profileObject id Object map Node Object functional blockNetwork variables Node Object NciLocation Location Label NviRequest Object RequestNvoStatus Object Status ACMotorDrive functional block Object map is the followingNetwork variable list VSD601011 LIUNetwork variable list the other NciMaxSpeed Maximum Speed Configuration propertiesNciMinSpeed Minimum Speed NciSndHrtBt Send Heartbeat Time NciRcvHrtBt Receive Heartbeat TimeNciMinOutTm Minimum Send Time NciNmlFreq Nominal Motor Frequency NciNmlSpeed Nominal Motor Speed in min-1NciRampUpTm Ramp Up Time NciPwUpOutTm Power up delay time NciDrvSpeedScale Default value for nviDrvSpeedScaleNciRampDownTm Ramp Down Time NviResetFault Fault Reset Command Input network variablesNviDrvSpeedStpt Drive Speed Setpoint NviDrvSpeedScale Drive Speed Setpoint Scaling NviInvSetFreq Frequency Setpoint NviRelay1 /nviDigitalOut1,2 Control of Digital Output NviDigitalOutput Control of All Digital Outputs LIU007Z LIU006ZNviAnalogOut1,2 Control of Analog output NviEmergOverride Emergency stopNviParamCmd Parameter access LnrecallLnlearncurrent LnlearnvalueOutput network variables NvoDrvFeedback Velocity Feedback NvoDrvAlarm AlarmNvoStatusWord Inverter Status NvoAlarmWord Alarm Status NvoDrvThermal Drive Thermal StateNvoMotorThermal Motor Thermal State NvoTorque Motor Torque MonitorNvoDigitalInput All Digital Inputs Monitor NvoDrvEnergy Cumulative Input EnergyNvoDigitalIn1 to 8 Digital Input Monitor NvoAnalogIn1 to 3 Analog Input Monitor NvoEmergStatus Emergency StatusNvoParamResp Parameter Access Response NvoTypeVer IdentificationAscii ToshibaProcedure Option unit reset methodExample usage BindingCommunication health management Parameter access method E6581373 Specifications ANSI/EIA/CEA