Toshiba TOSVERT VF-FS1 Series Configuration properties, NciMaxSpeed Maximum Speed

Page 20

E6581373

6.4. Configuration properties

6.4.1. nciMaxSpeed (Maximum Speed)

Configuration property (nc50), Variable Speed Drive 6010_11 (Mandatory) SNVT type: SNVT_lev_percent (81)

SCPT reference: SCPTmaxSetpoint (50)

It is used to define the maximum speed of the inverter output. The value is entered as a percent of nominal speed. The value of the maximum speed must be validated against the value of the minimum speed as follows:

-Valid range: 0.000 % minimum speed maximum speed 163.830 % (Limited within the value of the inverter parameter “ul” limitation)

-Unit: 0.005%

-Default Value: 100.000%

N.B.: By editing this variable, this option unit changes the inverter parameter “ul”, automatically. When setting small value, it may be limited by the lower limit of the inverter parameter “ul”

Danger

Prohibited

Do not set the value out of valid range.

Setting the value out of valid range may result in injuries by motor running with unexpected speed.

6.4.2. nciMinSpeed (Minimum Speed)

Configuration property, Variable Speed Drive 6010_11 (Mandatory) SNVT type: SNVT_lev_percent (81)

SCPT reference: SCPTminSetpoint (53)

It is used to define the minimum speed of the inverter output. The value is entered as a percent of nominal speed. The value of the minimum speed must be validated against the value of the maximum speed as follows:

-Valid range: 0.000 % minimum speed maximum speed 163.830 % (Limited within the value of the inverter parameter “ll” limitation)

-Unit: 0.005%

-Default Value: 0.000%

N.B.: By editing this variable, this option unit changes the inverter parameter “ll”, automatically.

Danger

Prohibited

Do not set the value out of valid range.

Setting the value out of valid range may result in injuries by motor running with unexpected speed.

- 19 -

Image 20
Contents E6581373 Introduction Handling in generalTable of Contents E6581373 System configuration ScopeOverview Applicable modelNames and functions of main parts Outline viewLIU006Z LIU007Z for VF-FS1LED DiagnosticsService LED Fault LED Status LEDLED on LED OFF OFFRS485 communication port Configurations Service pin Device interface XIF fileInverter configurations Neuron IDCommand & Setpoint selection Local/Remote LIU007ZReference parameter of the inverter Object id Functional profileFunctional profile supported by this option Network variables Node Object Node Object functional blockObject map NciLocation Location Label NviRequest Object RequestNvoStatus Object Status ACMotorDrive functional block Object map is the followingNetwork variable list VSD601011 LIUNetwork variable list the other NciMinSpeed Minimum Speed Configuration propertiesNciMaxSpeed Maximum Speed NciMinOutTm Minimum Send Time NciRcvHrtBt Receive Heartbeat TimeNciSndHrtBt Send Heartbeat Time NciRampUpTm Ramp Up Time NciNmlSpeed Nominal Motor Speed in min-1NciNmlFreq Nominal Motor Frequency NciRampDownTm Ramp Down Time NciDrvSpeedScale Default value for nviDrvSpeedScaleNciPwUpOutTm Power up delay time NviResetFault Fault Reset Command Input network variablesNviDrvSpeedStpt Drive Speed Setpoint NviDrvSpeedScale Drive Speed Setpoint ScalingNviInvSetFreq Frequency Setpoint NviRelay1 /nviDigitalOut1,2 Control of Digital OutputNviDigitalOutput Control of All Digital Outputs LIU007Z LIU006ZNviAnalogOut1,2 Control of Analog output NviEmergOverride Emergency stopNviParamCmd Parameter access LnrecallLnlearncurrent LnlearnvalueOutput network variables NvoStatusWord Inverter Status NvoDrvAlarm AlarmNvoDrvFeedback Velocity Feedback NvoAlarmWord Alarm Status NvoDrvThermal Drive Thermal StateNvoMotorThermal Motor Thermal State NvoTorque Motor Torque MonitorNvoDigitalIn1 to 8 Digital Input Monitor NvoDrvEnergy Cumulative Input EnergyNvoDigitalInput All Digital Inputs Monitor NvoAnalogIn1 to 3 Analog Input Monitor NvoEmergStatus Emergency StatusNvoParamResp Parameter Access Response NvoTypeVer IdentificationAscii ToshibaProcedure Option unit reset methodExample usage BindingCommunication health management Parameter access method E6581373 Specifications ANSI/EIA/CEA