E6581373
6.4.9. nciRampDownTm (Ramp Down Time)
Configuration property, Variable Speed Drive 6010_11 (Mandatory)
SNVT type: SNVT_time_sec (107)
SCPT reference: SCPTrampDownTm (161)
It determines the ramp down time of the motor.
-Valid range: 0.1 to 3200.0 sec.
-Unit: 0.1 sec.
-Default value: 10.0 sec.
N.B.: By editing this variable, this option unit changes the inverter parameter “dec” automatically.
6.4.10. nciDrvSpeedScale (Default value for nviDrvSpeedScale)
Configuration property, Variable Speed Drive 6010_11 (Optional) SNVT type: SNVT_lev_percent (81)
SCPT reference: SCPTdefScale (162)
It is used as the default value for “nviDrvSpeedScale”. When this option unit is initialized, it will be updated.
-Valid range:
-Unit: 0.005%
-Default value: 100.000%
6.4.11.nciPwUpOutTm (Power up delay time).
Configuration property
SNVT type: SNVT_time_sec (107)
SCPT reference: SCPTpwrUpDelay (72)
It defines the time until starting transmission after the device powered up. It is useful to improve network traffic at
-Valid range: 0.0 to 300.0 sec (If the value exceed 300.0, the value is limited to 300.0 sec)
-Unit: 0.1 sec.
-Default value: 0.0 sec.
- 22 -