Issue 10/06 | 3 Factory setting |
3 Factory setting
The MICROMASTER 440 frequency inverter is set in the factory so that it can be operated without any additional parameterization. To do this, the motor parameters set in the factory (P0304, P0305, P0307, P0310), that correspond to a
Further factory setting:
¾ Command sources P0700 = 2 (Digital input, see Fig.
¾ Setpoint source | P1000 = 2 (Analog input, see Fig. |
¾Motor cooling P0335 = 0
¾Motor current limit P0640 = 150 %
¾Min. frequency
P1080 = 0 Hz | Analog output |
¾Max. frequency P1082 = 50 Hz
¾
¾
¾Control mode P1300 = 0
|
| Fig. |
|
| ||
|
|
|
|
|
| |
Input/Output | Terminals | Parameter |
| Function |
| |
Digital input 1 | 5 | P0701 = 1 |
| ON / OFF1 | (I/O) | |
Digital input 2 | 6 | P0702 | = 12 |
| Reversing | ( ) |
Digital input 3 | 7 | P0703 | = 9 |
| Fault acknowledge | (Ack) |
Digital input 4 | 8 | P0704 | = 15 |
| Fault acknowledge |
|
Digital input 5 | 16 | P0705 | = 15 |
| Fixed setpoint (direct) |
|
Digital input 6 | 17 | P0706 | = 15 |
| Fixed setpoint (direct) |
|
Digital input 7 | Via ADC1 | P0707 | = 0 |
| Fixed setpoint (direct) |
|
Digital input 8 | Via ADC2 | P0708 | = 0 |
| Digital input disabled |
|
3.150/60 Hz DIP switch
The default motor base frequency of the MICROMASTER inverter is 50 Hz. For motors, which are designed for a base frequency of 60 Hz, the inverters can be set to this frequency using the DIP50/60 switch.
¾OFF position:
European defaults (Rated motor frequency = 50 Hz, Power in kW etc.)
Remove I/O board
DIP50/60
¾ON position:
North American defaults
(Rated motor frequency = 60 Hz, Power in hp etc.)
MICROMASTER 440 | 23 |
Operating Instructions (Compact) |