Siemens 440 50/60 Hz DIP switch, Pre-assignment of the inputs, Input/Output, Parameter Function

Page 23

Issue 10/06

3 Factory setting

3 Factory setting

The MICROMASTER 440 frequency inverter is set in the factory so that it can be operated without any additional parameterization. To do this, the motor parameters set in the factory (P0304, P0305, P0307, P0310), that correspond to a 4-pole 1LA7 Siemens motor, must match the rated data of the connected motor (refer to the rating plate).

Further factory setting:

¾ Command sources P0700 = 2 (Digital input, see Fig. 3-1)

¾ Setpoint source

P1000 = 2 (Analog input, see Fig. 3-1)

¾Motor cooling P0335 = 0

¾Motor current limit P0640 = 150 %

¾Min. frequency

P1080 = 0 Hz

Analog output

¾Max. frequency P1082 = 50 Hz

¾Ramp-up time P1120 = 10 s

¾Ramp-down time P1121 = 10 s

¾Control mode P1300 = 0

 

 

Fig. 3-1

 

Pre-assignment of the inputs

 

 

 

 

 

 

Input/Output

Terminals

Parameter

 

Function

 

Digital input 1

5

P0701 = 1

 

ON / OFF1

(I/O)

Digital input 2

6

P0702

= 12

 

Reversing

( )

Digital input 3

7

P0703

= 9

 

Fault acknowledge

(Ack)

Digital input 4

8

P0704

= 15

 

Fault acknowledge

 

Digital input 5

16

P0705

= 15

 

Fixed setpoint (direct)

 

Digital input 6

17

P0706

= 15

 

Fixed setpoint (direct)

 

Digital input 7

Via ADC1

P0707

= 0

 

Fixed setpoint (direct)

 

Digital input 8

Via ADC2

P0708

= 0

 

Digital input disabled

 

3.150/60 Hz DIP switch

The default motor base frequency of the MICROMASTER inverter is 50 Hz. For motors, which are designed for a base frequency of 60 Hz, the inverters can be set to this frequency using the DIP50/60 switch.

¾OFF position:

European defaults (Rated motor frequency = 50 Hz, Power in kW etc.)

Remove I/O board

DIP50/60

¾ON position:

North American defaults

(Rated motor frequency = 60 Hz, Power in hp etc.)

MICROMASTER 440

23

Operating Instructions (Compact)

Image 23
Contents User Documentation Operating Instructions Compact Issue 10/06Issue 10/06 Contents Contents Issue 10/06 Bolts Mounting dimensionsFrame Drilling Dimensions Tightening Torque Size Clearance distances for mountingInput voltage range Technical Specifications26,5 Weight Lbs 12,5Tightening torques for Power terminals Lbf.in Order No 6SE64401BA1 5BA1 Weight LbsOutput Power KVA Weight2AD31 Power terminals Lbf.in2AD23 2AD24 2AD27Output Cable, max Mm2 For UL specified Input Cable, min Mm2Input Cable, max Mm2 Output Cable, min Mm2Recommended Fuse 95 or 150 or 185 or 240 or4/0 or 300 or 400 or 500 or 1/0 2/0 350 or 4/05CA1 Order No 6SE6440 2UE17 2UE21 2UE22 2UE24 2UE25 2UE27 2UE31Frame Size a Power TerminalsRemoving front covers Frame Sizes B and C Frame Sizes B and CRemoving front covers Frame Sizes D and E Frame Sizes D and ERemoving front covers Frame Size F Frame Size FRemoving front covers Frame Sizes FX and GX Frame Sizes FX and GXConnection terminals for Frame Sizes a F Connection overview for Frame Size FX Connection overview for Frame Size GX Control terminals of Micromaster Control terminalsTerminal Designation Function FX and GX Block diagramFrame sizes To FParameter Function 50/60 Hz DIP switchPre-assignment of the inputs Input/OutputAOP at the BOP link AOP at the COM link PC frequency inverter connecting setEstablishing communications DeviceNet CANopen Bus interface CBAOP as control unit Parameter / Terminal AOP on BOP link AOP on COM linkButtons and their Functions Step Result on the display Quick commissioning Rated motor current Rated motor powerSelection of command source Rated motor voltageRamp-up time Selection of frequency setpointMin. frequency Max. frequencySelect motor data identification Control modeEnd of the quick commissioning/drive setting Selection of torque setpointSelect motor data identification with P1910 = Factory setting Ambient motor temperature entered in CMotor data identification Magnetizing currentDetermining the magnetizing current Quick commissioning routineMotor data identification routine Serial Interface USS Selection of command sourceCommissioning the application Debounce time for digital inputs Function digital input Possible SettingsDigital input DIN Function digital inputCO/BO State of digital outputs Common Settings ClosedDigital outputs Dout BI Function of digital outputExample P1000 = BI Disable additional setpointCommon settings Selection of frequency setpointAnalog input ADC Analog output DAC Setpoint of the MOP Motor potentiometer MOPSetpoint memory of the MOP Inhibit negative MOP setpointsFixed frequency FF JOG ramp-up time 10 JOGJOG frequency right JOG frequency leftRamp function generator RFG Reference/limit frequencies Motor protection Inverter temperature warningDelay, fan shutdown Inverter protectionMotor overload factor % Motor temperature sensorAlarm threshold, motor overtemperature Inverter temperature reactionEncoder Acceleration boost entered in % 16 V/f controlContinuous boost entered in % Programmable V/f freq .0 Hz Starting boost entered in %Programmable V/f freq Coord Programmable. V/f volt .0 HzLimitations Field-orientated controlSensorless vector control Slvc 17.1Zero crossing Operation directly after an on commandP1750 = Control word of motor modelGain speed controller 17.2Vector control with encoder VC Filter time for act. speedCI Supplementary torque setpoint Frequent settingsSupplementary torque setpoint P1511=Automatic restart Converter-specific FunctionsFlying start Motor size Brake type Opening time ms Closing time ms Holding brake enableHolding brake Holding time after ramp-down entered in s Holding brake release delay entered in sBI Fct digital output Inverting digital OutputsDC braking current entered in % DC brakeP1230 = P1232 = P1233 = BI Enabling the DC brakeCompound braking current entered in % Compound brakingDC braking start frequency entered in Hz Vdc controller Dynamic braking18.7 Load torque monitoring P2182 PID controller P2264 CI PID feedback Controller structuresParameter Parameter text Example PID cancer control Parameter Parameter text Setting MeaningPositioning down ramp Activate FFBs Enable FFBsFree function blocks FFB P2800 = P2801 = P2802 =Input parameters Output parameters Setting parameters Data sets Command data set CDSBI DDS bit Drive data set DDSP0820 = P0821 = Drive data set DDS bitDIN Diagnostic parameters CO Act. output voltage CO/BO Control wordCO Actual frequency CO Act. output current limitCO Freq. setpoint after dir. ctrl R1079CO Selected frequency setpoint R1114 R1170Series commissioning Parameter reset of factory settingFactory reset LED status display Displays and messagesAlarm Significance Fault messages and Alarm messagesFault Significance Internet Address Online Service & SupportRegional Contacts Central Technical Support