6.4.8Motor potentiometer (MOP)
P1031 =...
P1032 =...
P1040 =...
Setpoint memory of the MOP | 0 |
Saves last motor potentiometer setpoint (MOP) that was active before OFF command or power down.
0 MOP setpoint will not be stored
1 MOP setpoint will be stored (P1040 is updated)
Inhibit negative MOP setpoints | 1 | |
0 | Neg. MOP setpoint is allowed |
|
1 | Neg. MOP setpoint inhibited |
|
|
| |
Setpoint of the MOP | 5.00 Hz | |
Determines setpoint for motor potentiometer control. |
|
MOP
Possible parameter settings for the selection of MOP:
| Selection | MOP up | MOP down | |
DIN | P0719 = 0, P0700 = 2, P1000 = 1 | P0702 = 13 | P0703 = 14 | |
or | (DIN2) | (DIN3) | ||
| P0719 = 1, P0700 = 2 | |||
|
|
| ||
BOP | P0719 = 0, P0700 = 1, P1000 = 1 | UP button | DOWN button | |
or | ||||
| P0719 = 11 |
|
| |
USS on | P0719 = 0, P0700 = 4, P1000 = 1 | USS control word | USS control word | |
BOP link | or | r2032 Bit13 | r2032 Bit14 | |
P0719 = 41 | ||||
USS on | P0719 = 0, P0700 = 5, P1000 = 1 | USS control word | USS control word | |
COM link | or | r2036 Bit13 | r2036 Bit14 | |
P0719 = 51 | ||||
CB | P0719 = 0, P0700 = 6, P1000 = 1 | CB control word | CB control word | |
or | ||||
r2090 Bit13 | r2090 Bit14 | |||
| P0719 = 61 |