Issue 10/06 | 1 Installation |
1 Installation
1.1Clearance distances for mounting
The inverters can be mounted adjacent to each other. When mounting inverters one above the other, the specified environmental conditions must not be exceeded.
Independent of this, these minimum distances must be observed.
¾Frame Size A, B, C above and below 100 mm
¾Frame Size D, E above and below 300 mm
¾Frame Size F above and below 350 mm
¾ Frame Size FX, GX above 250 mm below 150 mm
in front 40 mm (FX), 50 mm (GX)
1.2Mounting dimensions
|
| Frame | Drilling Dimensions | Tightening Torque | ||
|
| Size |
|
|
|
|
|
|
| H | W | Bolts | Nm |
|
|
| mm (Inch) | mm (Inch) |
| (lbf.in) |
|
|
|
|
|
|
|
|
| A | 160 (6.30) | – | 2 x M4 | 2,5 |
|
|
|
|
|
| |
|
| B | 174 (6.85) | 138 (5.43) | 4 x M4 | |
|
| (22.12) | ||||
|
|
|
|
|
| |
|
| C | 204 (8.03) | 174 (6.85) | 4 x M5 |
|
H |
|
|
|
|
|
|
| D | 486 (19.13) | 235 (9.25) | 4 x M8 |
| |
|
|
|
|
|
|
|
|
| E | 616,4 | 235 (9.25) | 4 x M8 | 3,0 |
|
|
| (24.27) |
|
| |
W |
|
|
|
|
| (26.54) |
| F | 810 (31.89) | 300 (11.81) | 4 x M8 | ||
|
| |||||
|
|
|
|
|
|
|
|
| FX | 1375,5 | 250 (9.84) | 6 x M8 | 13,0 |
|
|
| (54.14) |
|
| |
|
|
|
|
| (115.02) | |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| GX | 1508,5 | 250 (9.84) | 6 x M8 | 13,0 |
|
|
| (59.38) |
|
| |
|
|
|
|
| (115.02) | |
|
|
|
|
|
| |
|
|
|
|
|
|
|
Fig. | Mounting dimensions |
|
|
|
MICROMASTER 440 | 5 |
Operating Instructions (Compact) |