Siemens 440 operating instructions Quick commissioning routine, Motor data identification routine

Page 33

Issue 10/06

6 Commissioning

The procedure to manually determine the magnetizing current and to re-calculate the equivalent circuit diagram data when the drive is operated with closed-loop vector control (P1300 = 20/21) is shown in the following.

START

Quick

commissioning

Motor data

identification

Operation under

no-load conditions

Criterium

fulfilled ?

no yes

P0320 = ...

P0340 = 1

END

Quick commissioning routine

Using the quick commissioning routine the frequency inverter is adapted to the motor and important technology parameters are set.

Motor data identification routine

Using the motor data identification routine motor equivalent circuit diagram data is determined using a measuring technique.

Determining the magnetizing current

In order to determine the magnetizing current (P0320/r0331), the motor should be accelerated up to approximately 80% of its rated speed under no-load operating conditions.

In so doing, the following conditions must be carefully maintained:

the vector control must be activated, P1300 = 20.21

no field weakening (r0056.8 = 0)

flux setpoint, r1598 = 100 %

no efficiency optimization, P1580 = 0 %

No-load operation means that the motor is operated without a load (i.e. no coupled driven machine).

Under steady-state conditions, a current r0027 is obtained that approximately corresponds to the rated magnetizing current r0331. (the current is always less than the no-load current for a pure V/f control).

Measuring and entering the magnetizing current and therefore the associated new calculation of the equivalent circuit diagram data of the motor is an iterative procedure. It must be repeated at least 2-3 times until the following criteria are fulfilled:

The more accurate the value of the magnetizing current that was entered, the better the flux setpoint (r1598=100%) matches the flux actual value (r0084=96..104%) of the observer model.

The output Xm adaptation (r1787) of the observer model should be as low as possible. Good values lie between 1-5%.The less that the Xh adaptation of the observer must operate, the sensitivity of the motor parameters after power failures are that much less sensitive.

NOTE

In order to display r0084 at the BOP/AOP, the LEVEL 4 parameters must be enabled using service parameter P3950=46.

Calculating P0320

 

0

Now, the new value can be entered in P0320 from the determined flux-

 

generating current component r0029 by applying the following equation.

 

P0320 = r0029 * 100 / P0305

 

Calculating the motor parameters

 

0

The values of the motor equivalent circuit diagram data are calculated from the entered rating plate data. In addition, the parameters of the controls are pre-set (subsequently optimized) (P0340 = 3).

MICROMASTER 440

33

Operating Instructions (Compact)

Image 33
Contents User Documentation Operating Instructions Compact Issue 10/06Issue 10/06 Contents Contents Issue 10/06 Frame Drilling Dimensions Tightening Torque Size Mounting dimensionsClearance distances for mounting BoltsInput voltage range Technical SpecificationsTightening torques for Power terminals Lbf.in Weight Lbs 12,5Order No 6SE6440 26,5Output Power KVA Weight LbsWeight 1BA1 5BA12AD23 2AD24 Power terminals Lbf.in2AD27 2AD31Input Cable, max Mm2 For UL specified Input Cable, min Mm2Output Cable, min Mm2 Output Cable, max Mm24/0 or 300 or 400 or 500 or 1/0 2/0 95 or 150 or 185 or 240 or350 or 4/0 Recommended Fuse5CA1 Order No 6SE6440 2UE17 2UE21 2UE22 2UE24 2UE25 2UE27 2UE31Frame Size a Power TerminalsRemoving front covers Frame Sizes B and C Frame Sizes B and CRemoving front covers Frame Sizes D and E Frame Sizes D and ERemoving front covers Frame Size F Frame Size FRemoving front covers Frame Sizes FX and GX Frame Sizes FX and GXConnection terminals for Frame Sizes a F Connection overview for Frame Size FX Connection overview for Frame Size GX Control terminals Terminal Designation FunctionControl terminals of Micromaster Frame sizes Block diagramTo F FX and GXPre-assignment of the inputs 50/60 Hz DIP switchInput/Output Parameter FunctionPC frequency inverter connecting set Establishing communicationsAOP at the BOP link AOP at the COM link AOP as control unit Bus interface CBParameter / Terminal AOP on BOP link AOP on COM link DeviceNet CANopenButtons and their Functions Step Result on the display Quick commissioning Selection of command source Rated motor powerRated motor voltage Rated motor currentMin. frequency Selection of frequency setpointMax. frequency Ramp-up timeEnd of the quick commissioning/drive setting Control modeSelection of torque setpoint Select motor data identificationMotor data identification Factory setting Ambient motor temperature entered in CMagnetizing current Select motor data identification with P1910 =Quick commissioning routine Motor data identification routineDetermining the magnetizing current Selection of command source Commissioning the applicationSerial Interface USS Digital input DIN Function digital input Possible SettingsFunction digital input Debounce time for digital inputsDigital outputs Dout Common Settings ClosedBI Function of digital output CO/BO State of digital outputsCommon settings BI Disable additional setpointSelection of frequency setpoint Example P1000 =Analog input ADC Analog output DAC Setpoint memory of the MOP Motor potentiometer MOPInhibit negative MOP setpoints Setpoint of the MOPFixed frequency FF JOG frequency right 10 JOGJOG frequency left JOG ramp-up timeRamp function generator RFG Reference/limit frequencies Delay, fan shutdown Inverter temperature warningInverter protection Motor protectionAlarm threshold, motor overtemperature Motor temperature sensorInverter temperature reaction Motor overload factor %Encoder 16 V/f control Continuous boost entered in %Acceleration boost entered in % Programmable V/f freq Coord Starting boost entered in %Programmable. V/f volt .0 Hz Programmable V/f freq .0 HzLimitations Field-orientated controlSensorless vector control Slvc 17.1P1750 = Operation directly after an on commandControl word of motor model Zero crossingVector control with encoder VC 17.2Filter time for act. speed Gain speed controllerSupplementary torque setpoint Frequent settingsP1511= CI Supplementary torque setpointConverter-specific Functions Flying startAutomatic restart Holding brake enable Holding brakeMotor size Brake type Opening time ms Closing time ms BI Fct digital output Holding brake release delay entered in sInverting digital Outputs Holding time after ramp-down entered in sP1230 = P1232 = P1233 = DC brakeBI Enabling the DC brake DC braking current entered in %Compound braking DC braking start frequency entered in HzCompound braking current entered in % Dynamic braking 18.7Vdc controller Load torque monitoring P2182 PID controller Controller structures Parameter Parameter text ExampleP2264 CI PID feedback PID cancer control Parameter Parameter text Setting MeaningPositioning down ramp Free function blocks FFB Enable FFBsP2800 = P2801 = P2802 = Activate FFBsInput parameters Output parameters Setting parameters Data sets Command data set CDSP0820 = P0821 = Drive data set DDSDrive data set DDS bit BI DDS bitDIN Diagnostic parameters CO Actual frequency CO/BO Control wordCO Act. output current limit CO Act. output voltageCO Selected frequency setpoint R1079R1114 R1170 CO Freq. setpoint after dir. ctrlParameter reset of factory setting Factory resetSeries commissioning LED status display Displays and messagesFault messages and Alarm messages Fault SignificanceAlarm Significance Regional Contacts Online Service & SupportCentral Technical Support Internet Address
Related manuals
Manual 328 pages 28.01 Kb