Issue 10/06 | 6 Commissioning |
r0054
r0063
CO/BO: Control word 1
Displays the first control word (STW) of the frequency inverter and can be used to display the active commands.
Bit00 | ON/OFF1 | 0 | NO | 1 | YES |
Bit01 | OFF2: Electrical stop | 0 | YES | 1 | NO |
Bit02 | OFF3: Fast stop | 0 | YES | 1 | NO |
Bit03 | Pulse enable | 0 | NO | 1 | YES |
Bit04 | RFG enable | 0 | NO | 1 | YES |
Bit05 | RFG start | 0 | NO | 1 | YES |
Bit06 | Setpoint enable | 0 | NO | 1 | YES |
Bit07 | Fault acknowledge | 0 | NO | 1 | YES |
Bit08 | JOG right | 0 | NO | 1 | YES |
Bit09 | JOG left | 0 | NO | 1 | YES |
Bit10 | Control from PLC | 0 | NO | 1 | YES |
Bit11 | Reverse (setpoint inversion) | 0 | NO | 1 | YES |
Bit13 | Motor potentiometer MOP up | 0 | NO | 1 | YES |
Bit14 | Motor potentiometer MOP down | 0 | NO | 1 | YES |
Bit15 | CDS Bit 0 (Local/Remote) | 0 | NO | 1 | YES |
CO: Actual frequency
Displays the actual frequency in Hz.
Frequency actual values:
V/f |
| |
SLVC |
| |
(observer |
| |
model) | P0400 | |
r0313 | ||
60 ⋅ P0408 | 0 | |
0 | ||
| ||
Encoder | 1,2 | |
|
60
r0313
Smoothed speed act. value
| 160 ms | r0022 |
|
| |
P1300 |
| Smoothed freq. actual value |
| r0021 | |
|
| |
<20 |
| Frequency actual value |
20,22 |
| r0063 |
21,23 |
|
|
Freq.act.value fr. the encoder r0061
r0067
r0072
P1300 = 21,23 and P0400 = 0
CO: Act. output current limit
Displays valid maximum output current of inverter.
| P0305 |
|
Motor | P0640 |
|
Motor protection |
| |
| r0067 | |
| Min | |
Inverter | r0209 |
|
Inverter protection |
| |
|
|
CO: Act. output voltage
Displays output voltage.
MICROMASTER 440 | 73 |
Operating Instructions (Compact) |