Siemens operating instructions Order No 6SE6440 2UE17 2UE21 2UE22 2UE24 2UE25 2UE27 2UE31, 5CA1

Page 12

2 Electrical Installation

Issue 10/06

Input voltage range

 

 

 

3 AC 500 V – 600 V, ± 10 %

 

(Unfiltered)

Order No.

6SE6440-

2UE17-

 

2UE21-

2UE22-

2UE24-

2UE25-

2UE27-

2UE31-

2UE31-

 

 

 

5CA1

 

5CA1

 

2CA1

 

0CA1

5CA1

5CA1

1CA1

5DA1

Frame Size

 

 

 

 

 

 

 

 

C

 

 

 

D

Output Rating(CT)

 

[kW]

0,75

 

1,5

 

2,2

 

4,0

5,5

7,5

11,0

15,0

 

[hp]

1,0

 

2,0

 

3,0

 

5,0

7,5

10,0

15,0

20,0

 

 

 

 

 

Output Power

 

[kVA]

1,3

 

2,6

 

3,7

 

5,8

8,6

10,5

16,2

21,0

CT-Input Current 1)

 

[A]

2,0

 

3,7

 

5,3

 

8,1

11,1

14,4

21,5

24,9

CT-Output Current

 

[A]

1,4

 

2,7

 

3,9

 

6,1

9,0

11,0

17,0

22,0

VT-Input Current 1)

 

[A]

3,2

 

4,4

 

6,9

 

9,4

12,6

18,1

24,9

30,0

VT-Output Current

 

[A]

2,7

 

3,9

 

6,1

 

9,0

11,0

17,0

22,0

27,0

Fuse

 

[A]

10

 

10

 

10

 

16

16

25

32

35

Recommended

 

3NA

3803-6

 

3803-6

 

3803-6

 

3805-6

3805-6

3810-6

3812-6

3814-6

For UL specified

 

3NE

*

 

*

 

*

 

*

*

*

*

1803-0

Input Cable, min.

 

[mm2]

1,0

 

1,0

 

1,0

 

1,5

1,5

2,5

4,0

6,0

 

[AWG]

18

 

18

 

18

 

16

16

14

12

10

 

 

 

 

 

Input Cable, max.

 

[mm2]

10,0

 

10,0

 

10,0

 

10,0

10,0

10,0

10,0

35,0

 

[AWG]

8

 

8

 

8

 

8

8

8

8

2

 

 

 

 

 

Output Cable, min.

 

[mm2]

1,0

 

1,0

 

1,0

 

1,0

1,0

2,5

4,0

4,0

 

[AWG]

18

 

18

 

18

 

18

18

14

12

12

 

 

 

 

 

Output Cable, max.

 

[mm2]

10,0

 

10,0

 

10,0

 

10,0

10,0

10,0

10,0

35,0

 

[AWG]

8

 

8

 

8

 

8

8

8

8

2

 

 

 

 

 

Weight

 

[kg]

5,5

 

5,5

 

5,5

 

5,5

5,5

5,5

5,5

16,0

 

[lbs]

12,1

 

12,1

 

12,1

 

12,1

12,1

12,1

12,1

35,0

 

 

 

 

 

Tightening torques for

 

[Nm]

 

 

 

 

 

2,25

 

 

 

10

power terminals

 

[lbf.in]

 

 

 

 

 

(20)

 

 

 

(89)

 

 

 

 

 

 

 

 

 

 

 

Order No.

6SE6440-

2UE31-

 

2UE32-

2UE33-

2UE33-

2UE34-

2UE35-

2UE37-

 

 

 

 

8DA1

 

2DA1

 

0EA1

 

7EA1

5FA1

5FA1

5FA1

 

Frame Size

 

 

 

D

 

 

E

 

F

 

 

Output Rating(CT)

 

[kW]

18,5

 

22,0

 

30,0

 

37,0

45,0

55,0

75,0

 

 

[hp]

25,0

 

30,0

 

40,0

 

50,0

60,0

75,0

100,0

 

 

 

 

 

 

 

Output Power

 

[kVA]

25,7

 

30,5

 

39,1

 

49,5

59,1

73,4

94,3

 

CT-Input Current 1)

 

[A]

30,0

 

35,0

 

48,0

 

58,0

69,0

83,0

113,0

 

CT-Output Current

 

[A]

27,0

 

32,0

 

41,0

 

52,0

62,0

77,0

99,0

 

VT-Input Current 1)

 

[A]

35,0

 

48,0

 

58,0

 

69,0

83,0

113,0

138,0

 

VT-Output Current

 

[A]

32,0

 

41,0

 

52,0

 

62,0

77,0

99,0

125,0

 

Fuse

 

[A]

50

 

63

 

80

 

80

125

160

160

 

Recommended

 

3NA

3820-6

 

3822-6

3824-6

 

3824-6

3132-6

3136-6

3136-6

 

For UL specified

 

3NE

1817-0

 

1818-0

1820-0

 

1820-0

1022-0

1224-0

1224-0

 

Input Cable, min.

 

[mm2]

10,0

 

10,0

 

16,0

 

25,0

25,0

50,0

50,0

 

 

[AWG]

8

 

8

 

6

 

3

3

1/0

1/0

 

 

 

 

 

 

 

Input Cable, max.

 

[mm2]

35,0

 

35,0

 

35,0

 

35,0

150,0

150,0

150,0

 

 

[AWG]

2

 

2

 

2

 

2

300

300

300

 

 

 

 

 

 

 

Output Cable, min.

 

[mm2]

6,0

 

10,0

 

16,0

 

16,0

25,0

35,0

50,0

 

 

[AWG]

10

 

8

 

6

 

6

3

2

1/0

 

 

 

 

 

 

 

Output Cable, max.

 

[mm2]

35,0

 

35,0

 

35,0

 

35,0

150,0

150,0

150,0

 

 

[AWG]

2

 

2

 

2

 

2

300

300

300

 

 

 

 

 

 

 

Weight

 

[kg]

16,0

 

16,0

 

20,0

 

20,0

56,0

56,0

56,0

 

 

[lbs]

35,0

 

35,0

 

44,0

 

44,0

123,0

123,0

123,0

 

 

 

 

 

 

 

Tightening torques for

 

[Nm]

 

 

 

10

 

 

 

50

 

 

power terminals

 

[lbf.in]

 

(89)

 

 

 

(445)

 

 

1)Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 500 V without line commutating reactor.

*UL listed fuses such as Class NON from Bussmann are required for use in America

12

MICROMASTER 440

Operating Instructions (Compact)

Image 12
Contents Operating Instructions Compact Issue 10/06 User DocumentationIssue 10/06 Contents Contents Issue 10/06 Mounting dimensions Frame Drilling Dimensions Tightening Torque SizeClearance distances for mounting BoltsTechnical Specifications Input voltage rangeWeight Lbs 12,5 Tightening torques for Power terminals Lbf.inOrder No 6SE6440 26,5Weight Lbs Output Power KVAWeight 1BA1 5BA1Power terminals Lbf.in 2AD23 2AD242AD27 2AD31For UL specified Input Cable, min Mm2 Input Cable, max Mm2Output Cable, min Mm2 Output Cable, max Mm295 or 150 or 185 or 240 or 4/0 or 300 or 400 or 500 or 1/0 2/0350 or 4/0 Recommended FuseOrder No 6SE6440 2UE17 2UE21 2UE22 2UE24 2UE25 2UE27 2UE31 5CA1Power Terminals Frame Size aFrame Sizes B and C Removing front covers Frame Sizes B and CFrame Sizes D and E Removing front covers Frame Sizes D and EFrame Size F Removing front covers Frame Size FFrame Sizes FX and GX Removing front covers Frame Sizes FX and GXConnection terminals for Frame Sizes a F Connection overview for Frame Size FX Connection overview for Frame Size GX Control terminals Terminal Designation FunctionControl terminals of Micromaster Block diagram Frame sizesTo F FX and GX50/60 Hz DIP switch Pre-assignment of the inputsInput/Output Parameter FunctionPC frequency inverter connecting set Establishing communicationsAOP at the BOP link AOP at the COM link Bus interface CB AOP as control unitParameter / Terminal AOP on BOP link AOP on COM link DeviceNet CANopenButtons and their Functions Step Result on the display Quick commissioning Rated motor power Selection of command sourceRated motor voltage Rated motor currentSelection of frequency setpoint Min. frequencyMax. frequency Ramp-up timeControl mode End of the quick commissioning/drive settingSelection of torque setpoint Select motor data identificationFactory setting Ambient motor temperature entered in C Motor data identificationMagnetizing current Select motor data identification with P1910 =Quick commissioning routine Motor data identification routineDetermining the magnetizing current Selection of command source Commissioning the applicationSerial Interface USS Function digital input Possible Settings Digital input DINFunction digital input Debounce time for digital inputsCommon Settings Closed Digital outputs DoutBI Function of digital output CO/BO State of digital outputsBI Disable additional setpoint Common settingsSelection of frequency setpoint Example P1000 =Analog input ADC Analog output DAC Motor potentiometer MOP Setpoint memory of the MOPInhibit negative MOP setpoints Setpoint of the MOPFixed frequency FF 10 JOG JOG frequency rightJOG frequency left JOG ramp-up timeRamp function generator RFG Reference/limit frequencies Inverter temperature warning Delay, fan shutdownInverter protection Motor protectionMotor temperature sensor Alarm threshold, motor overtemperatureInverter temperature reaction Motor overload factor %Encoder 16 V/f control Continuous boost entered in %Acceleration boost entered in % Starting boost entered in % Programmable V/f freq CoordProgrammable. V/f volt .0 Hz Programmable V/f freq .0 HzField-orientated control Limitations17.1 Sensorless vector control SlvcOperation directly after an on command P1750 =Control word of motor model Zero crossing17.2 Vector control with encoder VCFilter time for act. speed Gain speed controllerFrequent settings Supplementary torque setpointP1511= CI Supplementary torque setpointConverter-specific Functions Flying startAutomatic restart Holding brake enable Holding brakeMotor size Brake type Opening time ms Closing time ms Holding brake release delay entered in s BI Fct digital outputInverting digital Outputs Holding time after ramp-down entered in sDC brake P1230 = P1232 = P1233 =BI Enabling the DC brake DC braking current entered in %Compound braking DC braking start frequency entered in HzCompound braking current entered in % Dynamic braking 18.7Vdc controller Load torque monitoring P2182 PID controller Controller structures Parameter Parameter text ExampleP2264 CI PID feedback Parameter Parameter text Setting Meaning PID cancer controlPositioning down ramp Enable FFBs Free function blocks FFBP2800 = P2801 = P2802 = Activate FFBsInput parameters Output parameters Setting parameters Command data set CDS Data setsDrive data set DDS P0820 = P0821 =Drive data set DDS bit BI DDS bitDIN Diagnostic parameters CO/BO Control word CO Actual frequencyCO Act. output current limit CO Act. output voltageR1079 CO Selected frequency setpointR1114 R1170 CO Freq. setpoint after dir. ctrlParameter reset of factory setting Factory resetSeries commissioning Displays and messages LED status displayFault messages and Alarm messages Fault SignificanceAlarm Significance Online Service & Support Regional ContactsCentral Technical Support Internet Address