Issue 10/06 | 6 Commissioning |
6.4.5Selection of frequency setpoint
P1000 =...
Selection of frequency setpoint | 2 | ||
0 | No main setpoint |
|
|
1 | MOP setpoint |
|
|
2 | Analog setpoint |
|
|
3 | Fixed frequency |
|
|
4 | USS on BOP link |
|
|
5 | USS on COM link |
|
|
6 | CB on COM link |
|
|
7 | Analog setpoint 2 |
|
|
10 | No main setpoint | + MOP setpoint |
|
11 | MOP setpoint | + MOP setpoint |
|
12 | Analog setpoint | + MOP setpoint |
|
... |
|
|
|
76 | CB on COM link | + Analog setpoint 2 |
|
77 | Analog setpoint 2 | + Analog setpoint 2 |
|
NOTE
In addition to the main setpoint, a supplementary setpoint can be entered using P1000
Example P1000 = 12 :
P1000 = 12 ⇒ P1070 | = 755 | P1070 | CI: Main setpoint | ||
|
|
| |||
r0755 | CO: Act. ADC after scal. [4000h] | ||||
|
| ||||
|
|
|
| ||
P1000 = 12 ⇒ P1075 | = 1050 | P1075 | CI: Additional setpoint | ||
|
|
| |||
r1050 | CO: Act. Output freq. of the MOP | ||||
|
| ||||
|
|
|
|
|
MOP
ADC
FF
USS
BOP link
USS
COM link
CB
COM link
ADC2
P1076 | P1074 |
x
P1000 = 12
P1000 = 12
Additonal
setpoint
Main
setpoint
Sequence control
Setpoint |
|
| Motor |
channel |
|
| control |
| |||
|
|
|
|
P1074 = ...
P1076 = ...
BI: Disable additional setpoint | 0:0 |
Disables additional setpoint (ZUSW). |
|
|
|
CI: Additional setpoint scaling | 1:0 |
Defines the source to scale the additional setpoint. |
|
Common settings:
1Scaling of 1.0 (100 %)
755Analog input setpoint
1024 Fixed frequency setpoint
1050 MOP setpoint
MICROMASTER 440 | 37 |
Operating Instructions (Compact) |