Siemens 440 Inverter protection, Motor protection, Inverter overload reaction

Page 45

Issue 10/06

6 Commissioning

6.4.13

P0290 = ...

Inverter protection

Inverter overload reaction

0

Selects reaction of inverter to an internal over-temperature.

0Reduce output frequency

1Trip (F0004 / F0005)

2Reduce pulse frequency and output frequency

3Reduce pulse frequency then trip (F0004)

r0036

r0037

Inverter monitoring

i2t

P0294

Heat sink temperature P0292

IGBT

temperature

P0292

Inverter overload reaction

P0290

i_max control

(U/f)

Current control

(SLVC, VC)

f_pulse control

A0504

A0505

A0506

F0004

F0005

P0292 =...

P0295 = ...

Inverter temperature warning

15 °C

Defines the temperature difference (in ºC) between the Overtemperature trip threshold and the warning threshold of the inverter. The trip threshold is stored internally by the inverter and cannot be changed by the user.

Temperature warning threshold of inverter T_warn

Twarn = Ttrip - P0292

Temperature shutdown threshold of inverter T_trip

 

Temperature

 

 

 

 

MM440, Frame Size

 

 

 

 

A - C

 

D - F

 

F

 

FX

 

GX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600 V

 

95 kW

110 kW

132 kW

160 kW

200 kW

 

 

 

 

 

 

 

 

CT

CT

CT

CT

CT

 

Heat sink

110 °C

 

95 °C

 

80 °C

 

88 °C

91 °C

80 °C

82 °C

88 °C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IGBT

140 °C

 

145 °C

 

145 °C

 

150 °C

150 °C

145 °C

147 °C

150 °C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input rectifier

-

 

-

 

-

 

75 °C

75 °C

75 °C

75 °C

75 °C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling air

-

 

-

 

-

 

55 °C

55 °C

55 °C

55 °C

50 °C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control board

-

 

-

 

-

 

65 °C

65 °C

65 °C

65 °C

65 °C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Delay, fan shutdown

 

 

 

 

 

 

 

 

 

 

0 s

This defines the delay time in seconds between powering down the frequency inverter and then powering-down the fan. A setting of 0 means that the fan is immediately shut down (powered-down).

6.4.14Motor protection

In addition to the thermal motor protection, the motor temperature is also included in the adaptation of the motor equivalent circuit diagram data. Especially for a high thermal motor load, this adaptation has a significant influence on the degree of stability of the closed-loop vector control. For MM440 the motor temperature can only be measured using a KTY84 sensor. For the parameter setting P0601 = 0,1, the motor temperature is calculated / estimated using the thermal motor model.

If the frequency inverter is permanently supplied with an external 24V voltage, then the motor temperature is also tracked/corrected using the motor temperature time constant – even when the line supply voltage is switched-out.

MICROMASTER 440

45

Operating Instructions (Compact)

Image 45
Contents User Documentation Operating Instructions Compact Issue 10/06Issue 10/06 Contents Contents Issue 10/06 Frame Drilling Dimensions Tightening Torque Size Mounting dimensionsClearance distances for mounting BoltsInput voltage range Technical SpecificationsTightening torques for Power terminals Lbf.in Weight Lbs 12,5Order No 6SE6440 26,5Output Power KVA Weight LbsWeight 1BA1 5BA12AD23 2AD24 Power terminals Lbf.in2AD27 2AD31Input Cable, max Mm2 For UL specified Input Cable, min Mm2Output Cable, min Mm2 Output Cable, max Mm24/0 or 300 or 400 or 500 or 1/0 2/0 95 or 150 or 185 or 240 or350 or 4/0 Recommended Fuse5CA1 Order No 6SE6440 2UE17 2UE21 2UE22 2UE24 2UE25 2UE27 2UE31Frame Size a Power TerminalsRemoving front covers Frame Sizes B and C Frame Sizes B and CRemoving front covers Frame Sizes D and E Frame Sizes D and ERemoving front covers Frame Size F Frame Size FRemoving front covers Frame Sizes FX and GX Frame Sizes FX and GXConnection terminals for Frame Sizes a F Connection overview for Frame Size FX Connection overview for Frame Size GX Control terminals Terminal Designation FunctionControl terminals of Micromaster Frame sizes Block diagramTo F FX and GXPre-assignment of the inputs 50/60 Hz DIP switchInput/Output Parameter FunctionPC frequency inverter connecting set Establishing communicationsAOP at the BOP link AOP at the COM link AOP as control unit Bus interface CBParameter / Terminal AOP on BOP link AOP on COM link DeviceNet CANopenButtons and their Functions Step Result on the display Quick commissioning Selection of command source Rated motor powerRated motor voltage Rated motor currentMin. frequency Selection of frequency setpointMax. frequency Ramp-up timeEnd of the quick commissioning/drive setting Control modeSelection of torque setpoint Select motor data identificationMotor data identification Factory setting Ambient motor temperature entered in CMagnetizing current Select motor data identification with P1910 =Quick commissioning routine Motor data identification routineDetermining the magnetizing current Selection of command source Commissioning the applicationSerial Interface USS Digital input DIN Function digital input Possible SettingsFunction digital input Debounce time for digital inputsDigital outputs Dout Common Settings ClosedBI Function of digital output CO/BO State of digital outputsCommon settings BI Disable additional setpointSelection of frequency setpoint Example P1000 =Analog input ADC Analog output DAC Setpoint memory of the MOP Motor potentiometer MOPInhibit negative MOP setpoints Setpoint of the MOPFixed frequency FF JOG frequency right 10 JOGJOG frequency left JOG ramp-up timeRamp function generator RFG Reference/limit frequencies Delay, fan shutdown Inverter temperature warningInverter protection Motor protectionAlarm threshold, motor overtemperature Motor temperature sensorInverter temperature reaction Motor overload factor %Encoder 16 V/f control Continuous boost entered in %Acceleration boost entered in % Programmable V/f freq Coord Starting boost entered in %Programmable. V/f volt .0 Hz Programmable V/f freq .0 HzLimitations Field-orientated controlSensorless vector control Slvc 17.1P1750 = Operation directly after an on commandControl word of motor model Zero crossingVector control with encoder VC 17.2Filter time for act. speed Gain speed controllerSupplementary torque setpoint Frequent settingsP1511= CI Supplementary torque setpointConverter-specific Functions Flying startAutomatic restart Holding brake enable Holding brakeMotor size Brake type Opening time ms Closing time ms BI Fct digital output Holding brake release delay entered in sInverting digital Outputs Holding time after ramp-down entered in sP1230 = P1232 = P1233 = DC brakeBI Enabling the DC brake DC braking current entered in %Compound braking DC braking start frequency entered in HzCompound braking current entered in % Dynamic braking 18.7Vdc controller Load torque monitoring P2182 PID controller Controller structures Parameter Parameter text ExampleP2264 CI PID feedback PID cancer control Parameter Parameter text Setting MeaningPositioning down ramp Free function blocks FFB Enable FFBsP2800 = P2801 = P2802 = Activate FFBsInput parameters Output parameters Setting parameters Data sets Command data set CDSP0820 = P0821 = Drive data set DDSDrive data set DDS bit BI DDS bitDIN Diagnostic parameters CO Actual frequency CO/BO Control wordCO Act. output current limit CO Act. output voltageCO Selected frequency setpoint R1079R1114 R1170 CO Freq. setpoint after dir. ctrlParameter reset of factory setting Factory resetSeries commissioning LED status display Displays and messagesFault messages and Alarm messages Fault SignificanceAlarm Significance Regional Contacts Online Service & SupportCentral Technical Support Internet Address