Siemens 440 operating instructions Motor data identification, Magnetizing current

Page 32

6 Commissioning

Issue 10/06

6.2Motor data identification

START

P0625 = ?

Motor temp. - P0625

5 °C ?

yes no

Allow the motor

to cool down

P1910 = 1

A0541

ON

OFF1

P1910 = 3

A0541

ON

OFF1

END

Factory setting

Ambient motor temperature (entered in °C)

20 °C

The motor ambient temperature is entered at the instant that motor data is being determined (factory setting: 20 °C).

The difference between the motor temperature and the motor ambient temperature P0625 must lie in the tolerance range of approx. ± 5 °C. If this is not the case, then the motor data identification routine can only be carried-out after the motor has cooled down.

Select motor data identification with P1910 = 1

0

p1910 = 1: Identifies the motor parameter with parameter change. These are accepted and applied to the controller.

When p1910 = 1 is selected, Alarm A0541 (motor data identification active) is output, and internally p0340 is set to 3.

Starts the motor data identification run with p1910 = 1

The measuring operation is initiated with the continuous (steady-state) ON command. The motor aligns itself and current flows through it. Diagnostics is possible using r0069 (CO: Phase current).

After the motor data identification routine has been completed, p1910 is reset (p1910 = 0, motor data identification routine inhibited) and Alarm A0541 is cleared (deleted).

In order to set the frequency converter into a defined state, an OFF1 command must be issued before the next step.

Select motor data identification with P1910 = 3

0

p1910 = 3: Identifies the saturation characteristic with parameter change.

When p1910 = 3 is selected, Alarm A0541 (motor data identification active) is output and internally, p0340 is set to 2.

Starts the motor data identification run with P1910 = 3

The measuring operation must be started with a continuous ON command. After the motor identification routine has been completed, p1910 is reset (p1910 = 0, motor data identification routine inhibited) and Alarm A0541 is cleared (deleted).

In order to set the frequency converter into a defined state, an OFF1 command must be issued before the next step.

6.3Magnetizing current

¾The value of the magnetizing current r0331/P0320 has a significant influence on the closed-loop control. This cannot be measured at standstill. This means that the value is estimated for standard 4-pole 1LA7 Siemens standard using the automatic parameterization P0340=1 (P0320=0; result in r0331).

¾If the deviation of the magnetizing current is too high, then the values for the magnetizing reactance and those of the rotor resistance will not be able to be accurately determined.

¾Especially for third-party motors it is important that the magnetizing current that is determined, is carefully checked and if required, appropriately corrected.

32

MICROMASTER 440

Operating Instructions (Compact)

Image 32
Contents Operating Instructions Compact Issue 10/06 User DocumentationIssue 10/06 Contents Contents Issue 10/06 Mounting dimensions Frame Drilling Dimensions Tightening Torque SizeClearance distances for mounting BoltsTechnical Specifications Input voltage rangeWeight Lbs 12,5 Tightening torques for Power terminals Lbf.inOrder No 6SE6440 26,5Weight Lbs Output Power KVAWeight 1BA1 5BA1Power terminals Lbf.in 2AD23 2AD242AD27 2AD31For UL specified Input Cable, min Mm2 Input Cable, max Mm2Output Cable, min Mm2 Output Cable, max Mm295 or 150 or 185 or 240 or 4/0 or 300 or 400 or 500 or 1/0 2/0350 or 4/0 Recommended FuseOrder No 6SE6440 2UE17 2UE21 2UE22 2UE24 2UE25 2UE27 2UE31 5CA1Power Terminals Frame Size aFrame Sizes B and C Removing front covers Frame Sizes B and CFrame Sizes D and E Removing front covers Frame Sizes D and EFrame Size F Removing front covers Frame Size FFrame Sizes FX and GX Removing front covers Frame Sizes FX and GXConnection terminals for Frame Sizes a F Connection overview for Frame Size FX Connection overview for Frame Size GX Control terminals of Micromaster Control terminalsTerminal Designation Function Block diagram Frame sizesTo F FX and GX50/60 Hz DIP switch Pre-assignment of the inputsInput/Output Parameter FunctionAOP at the BOP link AOP at the COM link PC frequency inverter connecting setEstablishing communications Bus interface CB AOP as control unitParameter / Terminal AOP on BOP link AOP on COM link DeviceNet CANopenButtons and their Functions Step Result on the display Quick commissioning Rated motor power Selection of command sourceRated motor voltage Rated motor currentSelection of frequency setpoint Min. frequencyMax. frequency Ramp-up timeControl mode End of the quick commissioning/drive settingSelection of torque setpoint Select motor data identificationFactory setting Ambient motor temperature entered in C Motor data identificationMagnetizing current Select motor data identification with P1910 =Determining the magnetizing current Quick commissioning routineMotor data identification routine Serial Interface USS Selection of command sourceCommissioning the application Function digital input Possible Settings Digital input DINFunction digital input Debounce time for digital inputsCommon Settings Closed Digital outputs DoutBI Function of digital output CO/BO State of digital outputsBI Disable additional setpoint Common settingsSelection of frequency setpoint Example P1000 =Analog input ADC Analog output DAC Motor potentiometer MOP Setpoint memory of the MOPInhibit negative MOP setpoints Setpoint of the MOPFixed frequency FF 10 JOG JOG frequency rightJOG frequency left JOG ramp-up timeRamp function generator RFG Reference/limit frequencies Inverter temperature warning Delay, fan shutdownInverter protection Motor protectionMotor temperature sensor Alarm threshold, motor overtemperatureInverter temperature reaction Motor overload factor %Encoder Acceleration boost entered in % 16 V/f controlContinuous boost entered in % Starting boost entered in % Programmable V/f freq CoordProgrammable. V/f volt .0 Hz Programmable V/f freq .0 HzField-orientated control Limitations17.1 Sensorless vector control SlvcOperation directly after an on command P1750 =Control word of motor model Zero crossing17.2 Vector control with encoder VCFilter time for act. speed Gain speed controllerFrequent settings Supplementary torque setpointP1511= CI Supplementary torque setpointAutomatic restart Converter-specific FunctionsFlying start Motor size Brake type Opening time ms Closing time ms Holding brake enableHolding brake Holding brake release delay entered in s BI Fct digital outputInverting digital Outputs Holding time after ramp-down entered in sDC brake P1230 = P1232 = P1233 =BI Enabling the DC brake DC braking current entered in %Compound braking current entered in % Compound brakingDC braking start frequency entered in Hz Vdc controller Dynamic braking18.7 Load torque monitoring P2182 PID controller P2264 CI PID feedback Controller structuresParameter Parameter text Example Parameter Parameter text Setting Meaning PID cancer controlPositioning down ramp Enable FFBs Free function blocks FFBP2800 = P2801 = P2802 = Activate FFBsInput parameters Output parameters Setting parameters Command data set CDS Data setsDrive data set DDS P0820 = P0821 =Drive data set DDS bit BI DDS bitDIN Diagnostic parameters CO/BO Control word CO Actual frequencyCO Act. output current limit CO Act. output voltageR1079 CO Selected frequency setpointR1114 R1170 CO Freq. setpoint after dir. ctrlSeries commissioning Parameter reset of factory settingFactory reset Displays and messages LED status displayAlarm Significance Fault messages and Alarm messagesFault Significance Online Service & Support Regional ContactsCentral Technical Support Internet Address
Related manuals
Manual 328 pages 28.01 Kb