6 Commissioning
6.1Quick commissioning
The frequency inverter is adapted to the motor using the quick commissioning function and important technological parameters are set. The quick commissioning shouldn't be
Parameters, designated with a * offer more setting possibilities than are actually listed here. Refer to the parameter list for additional setting possibilities.
START
Factory setting
|
| User access level * | 1 | ||
P0003 = 3 | |||||
| |||||
| 1 | Standard: Allows access into most frequently used parameters |
| ||
|
| ||||
| 2 | Extended: Allows extended access e.g. to inverter I/O functions |
| ||
| 3 | Expert (For expert use only) |
| ||
|
|
|
|
|
| Parameter filter * | 0 | |
P0004 = 0 | |||
|
0All parameters
2Inverter
3Motor
4Speed sensor
|
| Commissioning parameter * | 0 | ||
P0010 = 1 | |||||
| |||||
| 0 | Ready |
| ||
|
| ||||
| 1 | Quick commissioning |
| ||
| 30 | Factory setting |
|
|
|
| NOTE |
|
|
|
| |
|
|
| P0010 should be set to 1 in order to parameterize the data of the motor rating | |||||
|
|
| plate. |
|
|
|
| |
P0100 =... | Europe/ North America |
| 0 | |||||
(enters the line supply frequency) |
| |||||||
|
|
|
| |||||
2 |
| P0100= 0 | 0 | Europe [kW], frequency default 50 Hz |
| |||
P0100= 1, |
| 1 | North America [hp], frequency default 60 Hz |
| ||||
| 2 | North America [kW], frequency default 60 Hz |
| |||||
| For P0100 = 0 or 1, the setting of switch DIP50/60 determines the value of |
| ||||||
|
|
| NOTE |
|
|
|
| |
|
|
| P0100. |
|
|
|
| |
|
|
|
| OFF | = | kW, 50 Hz |
| |
|
|
|
| ON | = | hp, 60 Hz |
| |
|
|
|
|
|
| |||
|
| P0205 =... | Inverter application (enters the required torque) |
| 0 | |||
P0205 =... |
|
| ||||||
|
| |||||||
|
|
| 0 | Constant torque (e.g. compressors, processing machines) |
| |||
|
|
|
| |||||
|
|
| 1 | Variable torque (e.g. pumps, fans) |
| |||
|
|
| NOTE |
|
|
|
| |
|
|
| This parameter is only effective for drive inverters ≥ 5.5 kW / 400 V |
| ||||
|
|
|
|
|
| |||
|
| P0300 =... | Select motor type |
| 1 | |||
P0300 =... |
|
| ||||||
|
|
1Asynchronous motor (induction motor)
2Synchronous motor
NOTE
For P0300 = 2 (synchronous motor), only the V/f control types (P1300 < 20) are permitted.