Emerson 5400, 5300 specifications Establish Hart Communication, Connect to the MA/MB terminals

Page 10

Rosemount 5300/5400 Series

Manual Supplement

00809-0500-4530, Rev AA October 2010

ESTABLISH HART

COMMUNICATION

Connect to the MA/MB terminals

Figure 1-8. RS-485 Communication after startup

The Rosemount 5300 Series and Rosemount 5400 Series can be configured using the Rosemount Radar Master (RRM) PC software or a Field Communicator. Configuration is done by sending HART commands through the HART to Modbus Converter (HMC) to the 5300/5400 transmitter electronics. To establish HART communication, connect to the MA/MB terminals, or to the HART terminals. Both alternatives are described below.

The 5300/5400 level transmitter can be configured with RRM using the MA, MB terminals.

An RS-485 Converter is required to connect to the transmitter.

The transmitter will try to establish communication using different protocols during 20 second timeslots from time of startup.

 

 

 

 

Configured

 

 

 

Configured

 

 

 

 

 

 

protocol

 

 

 

protocol

 

 

 

Modbus RTU

 

HART

 

(Modbus RTU,

 

HART

 

(Modbus RTU,

 

 

20 seconds

 

20 seconds

 

Levelmaster,

 

20 seconds

 

Levelmaster,

 

 

 

 

 

 

or Modbus

 

 

 

or Modbus

 

 

 

 

 

 

 

ASCII)

 

 

 

ASCII)

 

Time

 

 

 

 

20 seconds

 

 

 

20 seconds

 

 

 

 

 

 

 

 

 

 

 

0 s

20 s

40 s

60 s

80 s

100 s

The transmitter will continue to use a communication protocol once communication has been established.

1-10

Image 10
Contents Rosemount 5300/5400 Series with Hart to Modbus Converter Manual SupplementSafety Messages Explosions could result in death or serious injuryIntroduction WorkflowMechanical Installation Electrical Installation Field Wiring Connections Hart + Installation cases RS-485 BusStar Topology Alternative Multidrop Connection of 5300/5400 TransmittersNo. of devices Approx. update rate Slaves External Hart Devices SlavesEstablish Hart Communication Connect to the MA/MB terminalsRosemount 5300/5400 Series Connect to the Hart terminals Transmitter Configuration Modbus Communication Protocol Configuration Using RRM to change communication parametersModbus Setup Modbus RTU Parameter Configuration Example HMC A44 B4800 PO S2 Levelmaster Communication SetupHMC A127 Levelmaster Parameter Configuration Example HMC M2 A2 B9600 D7 PN S1Implemented Functions of Levelmaster Protocol Modbus Ascii Communication Setup HMC M1 A246 B9600 D7 PN S1Rosemount 5300/5400 Series Alarm Handling Levelmaster Modbus RTUModbus Ascii Rosemount 5300/5400 Series Common Modbus Host Configuration Input RegistersBit information in bitfield 14. Output Variables for Floating Point Format Code Rosemount 5300/5400 Series Volume Length Measurement UnitsSpecific Modbus Host Configuration Emerson Process Management ROC800 SeriesEmerson Process Management FloBoss ABB TotalFlowThermo Electron Autopilot Bristol ControlWave MicroScadaPack Kimray Dacc 2000/3000No communication with Modbus RTU protocol Troubleshooting No communication on RS-485 bus MA, MBNo 5300/5400 communication in RRM No communication with Modbus Ascii protocolHMC Firmware Upgrade in Rosemount Radar Master Select Enable Modbus Communication and click OKRosemount 5300/5400 Series Click Browse Checksum Rosemount 5300/5400 Series Specifications Rosemount 5300/5400 Series Emerson Process Management Rosemount Measurement