Manual Supplement
Rosemount 5300/5400 Series
Emerson Process Management FloBoss 107
Figure 1-10. Wiring Diagram for Connecting 5300/5400 Modbus to Emerson Process Management FloBoss 107
|
|
|
|
| FloBoss 107 | |
5300/5400 Modbus |
|
|
| |||
MA |
|
|
|
| A | |
|
|
|
| |||
MB |
|
|
|
| B | |
|
|
|
| |||
POWER + |
|
|
| NC | ||
|
|
| ||||
POWER - |
|
|
| NC | ||
|
|
| ||||
|
|
|
|
| PWR | |
|
| |||||
|
|
|
|
| GND | |
Power Supply | ||||||
|
|
|
| |||
+ 8 to + 30 Vdc |
|
|
|
| ||
(max. rating) |
|
|
|
| ||
GND |
|
|
|
| ||
|
|
|
|
Table
ABB TotalFlow
Figure 1-11. Wiring diagram for connecting 5300/5400 Modbus to ABB TotalFlow
Table 1-21. Parameter Values (in case of ABB TotalFlow)
Parameter | Value |
Baud Rate | 9600 |
Floating Point Format Code | 0 |
RTU Data Type | Conversion Code 66 |
Input Register Base Number | 0 |
|
|
The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1300 needs to have 1300 entered as the address.
Parameter | Value |
Baud Rate | 9600 |
Floating Point Format Code | 0 |
RTU Data Type | 16 Bit Modicon |
Input Register Base Number | 1 |
|
|
The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1302 needs to have 1303 entered as the address etc.