Emerson 5300, 5400 specifications Emerson Process Management FloBoss, ABB TotalFlow

Page 31

Manual Supplement

00809-0500-4530, Rev AA October 2010

Rosemount 5300/5400 Series

Emerson Process Management FloBoss 107

Figure 1-10. Wiring Diagram for Connecting 5300/5400 Modbus to Emerson Process Management FloBoss 107

 

 

 

 

 

FloBoss 107

5300/5400 Modbus

 

 

 

RS-485

MA

 

 

 

 

A

 

 

 

 

MB

 

 

 

 

B

 

 

 

 

POWER +

 

 

 

NC

 

 

 

POWER -

 

 

 

NC

 

 

 

 

 

 

 

 

PWR

 

 

 

 

 

 

 

GND

Power Supply

 

 

 

 

+ 8 to + 30 Vdc

 

 

 

 

(max. rating)

 

 

 

 

GND

 

 

 

 

 

 

 

 

Table 1-20. Parameter Values (in case of Emerson Process Management FloBoss 107)

ABB TotalFlow

Figure 1-11. Wiring diagram for connecting 5300/5400 Modbus to ABB TotalFlow

Table 1-21. Parameter Values (in case of ABB TotalFlow)

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

Conversion Code 66

Input Register Base Number

0

 

 

The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1300 needs to have 1300 entered as the address.

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

16 Bit Modicon

Input Register Base Number

1

 

 

The Input Register Base Number needs to be added to the Input Register address of the 5300/5400 transmitter. In this case, register 1302 needs to have 1303 entered as the address etc.

1-31

Image 31
Contents Manual Supplement Rosemount 5300/5400 Series with Hart to Modbus ConverterExplosions could result in death or serious injury Safety MessagesWorkflow IntroductionMechanical Installation Electrical Installation Field Wiring Connections Hart + RS-485 Bus Installation casesAlternative Multidrop Connection of 5300/5400 Transmitters Star TopologyExternal Hart Devices Slaves No. of devices Approx. update rate SlavesConnect to the MA/MB terminals Establish Hart CommunicationRosemount 5300/5400 Series Connect to the Hart terminals Transmitter Configuration Using RRM to change communication parameters Modbus Communication Protocol ConfigurationModbus Setup Modbus RTU Parameter Configuration Example HMC A44 B4800 PO S2 Levelmaster Communication SetupHMC A127 HMC M2 A2 B9600 D7 PN S1 Levelmaster Parameter Configuration ExampleImplemented Functions of Levelmaster Protocol HMC M1 A246 B9600 D7 PN S1 Modbus Ascii Communication SetupRosemount 5300/5400 Series Alarm Handling Levelmaster Modbus RTUModbus Ascii Rosemount 5300/5400 Series Input Registers Common Modbus Host ConfigurationBit information in bitfield 14. Output Variables for Floating Point Format Code Rosemount 5300/5400 Series Measurement Units Volume LengthEmerson Process Management ROC800 Series Specific Modbus Host ConfigurationABB TotalFlow Emerson Process Management FloBossBristol ControlWave Micro Thermo Electron AutopilotKimray Dacc 2000/3000 ScadaPackNo communication with Modbus Ascii protocol Troubleshooting No communication on RS-485 bus MA, MBNo 5300/5400 communication in RRM No communication with Modbus RTU protocolSelect Enable Modbus Communication and click OK HMC Firmware Upgrade in Rosemount Radar MasterRosemount 5300/5400 Series Click Browse Checksum Rosemount 5300/5400 Series Specifications Rosemount 5300/5400 Series Emerson Process Management Rosemount Measurement